Rosemount 3051N
2-2
FAILURE MODE ALARM
Rosemount 3051N transmitters automatically and continuously perform 
self-diagnostic routines. If the self-diagnostic routines detect a failure, the 
transmitter drives its output outside of the normal saturation values. The 
transmitter will drive its output low or high based on the position of the failure 
mode alarm jumper. See Table 2-1 for failure mode and saturation output 
levels. To select alarm position, see “Configuring Transmitter Alarm and 
Security Jumper Procedure” in Section 2.
Table 2-1.  Standard Alarm and 
Saturation Values.
NOTE
You can alter the actual transmitter mA output values by performing an analog 
output trim.
NOTE
When a transmitter is in an alarm condition, the hand-held HART 
Communicator indicates the analog output the transmitter would drive if the 
alarm condition did not exist. The transmitter will alarm high in the event of 
failure if the alarm jumper is removed.
Alarm Level Verification
Transmitters allow verification testing of alarm current levels. If you replace 
the LCD meter, reconfigure or make any changes to the transmitter, verify the 
transmitter alarm level before you return the transmitter to service. This 
feature is also useful in testing the reaction of your control system to a 
transmitter in an alarm state. To verify the transmitter alarm values, perform a 
loop test and set the transmitter output to the alarm value (see Table 2-1 and 
“Loop Test” in Section 2).
TRANSMITTER 
SECURITY
There are three security methods with the Rosemount 3051N transmitter:
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present 
on leads can cause electrical shock.
Level
4–20 mA
Saturation
4–20 mA
Alarm
Low
3.9 mA
≤ 3.75 mA
High
20.8 mA
≥ 21.75 mA