Rosemount 3051N
Recall Factory Trim
The Recall Factory Trim commands allow the restoration of the as-shipped 
factory settings of the sensor trim and analog output trim.
Recall Factory Trim— 
Sensor Trim
Resets the transmitter sensor trim to the as-shipped factory settings. The 
Recall Factory Trim—Sensor Trim command can be useful for recovering 
from an inadvertent zero trim of an absolute pressure unit.
Recall Factory Trim— 
Analog Output
Resets the transmitter analog output trim to the as-shipped
factory settings. The Recall Factory Trim—Analog Output Trim command can 
be useful for recovering from an inadvertent zero trim on an absolute pressure 
transmitter.
Analog Output Trim
The Analog Output Trim commands allow you to adjust the transmitter’s 
current output at the 4 and 20 mA points to match the plant standards. This 
command adjusts the digital to analog signal conversion (see Figure 2-7).
Digital-to-Analog Trim
To perform a digital-to-analog trim with a HART Communicator, perform the 
following procedure.
1.
From the 
ONLINE
 screen, select 1 Device setup, 2 Diag/Service, 
3 Calibration, 2 Trim Analog Output, 1 Digital-to-Analog Trim. Select 
OK
 after you set the control loop to manual (see “Setting the Loop to 
2.
Connect an accurate reference ammeter to the transmitter at the 
CONNECT REFERENCE METER
 prompt. To do so, connect the 
positive lead to the positive terminal and the negative lead to the test 
terminal in the transmitter terminal compartment, or shunt the 
transmitter power through the reference meter at some point.
3.
Select 
OK
 after connecting the reference meter.
4.
Select 
OK
 at the 
SETTING FLD DEV OUTPUT TO 4 MA
 prompt. The 
transmitter outputs 4.00 mA.
5.
Record the actual value from the reference meter, and enter it at the 
ENTER METER VALUE
 prompt. The communicator prompts you to 
verify whether or not the output value equals the value on the 
reference meter.
6.
Select 1 Yes if the reference meter value equals the transmitter 
output value, or 2 No if it does not.
IF you select 1 Yes, THEN proceed to Step 7.
IF you select 2 No, THEN repeat Step 5.
7.
Select 
OK
 at the 
SETTING FLD DEV OUTPUT TO 20 MA
 prompt, 
and repeat Steps 5 and 6 until the reference meter value equals the 
transmitter output value.
8.
Select 
OK
 after you return the control loop to automatic control.
Digital-to-Analog Trim 
Using Other Scale
The Scaled D/A Trim command matches the 4 and 20 mA points to a 
user-selectable reference scale other than 4 and 20 mA (1 to 5 volts if 
measuring across a 250 ohm load, or 0 to 100 percent if measuring from a 
DCS, for example). To perform a scaled D/A trim, connect an accurate 
reference meter to the transmitter and trim the output signal to scale as 
outlined in the Output Trim procedure.
HART Comm.
1, 2, 3, 4, 1
HART Comm.
1, 2, 3, 4, 2
HART Comm.
1, 2, 3, 2, 1
HART Comm.
1, 2, 3, 2, 2