Installation
510977
20
Connecting Power Cord with Three-Wire Plug
NOTE: Four-wire cord is required for mobile 
homes or where codes do not permit grounding 
through neutral.
Figure 13 
1. Disconnect power to dryer.
2. Remove access cover from rear of dryer.
Figure 14 
3. Use a strain relief and insert end of power cord 
through power supply hole.
Figure 15 
D816I
1
3 Wire Grounded Neutral 120/240 Volt, 60 Hertz 
AC 1 Phase Service Entrance Switch Box
(Refer to NOTE above)
4
Metallic or Non-Metallic Sheathed Cable 
(Copper Wire Only)
5
Power Cord (Not supplied with dryer)
2
30 Ampere Fuses or Circuit Breaker
6
Neutral
3
Neutral Wire
7
Terminal Block in Dryer
NOTE: The power cord is NOT supplied with the 
electric dryer. Type of power cord and gauge of wire 
must conform to local codes and instructions.
The method of wiring the dryer is optional and subject 
to local code requirements.
NOTE: Connect the dryer to the power supply with the 
MAXIMUM RATED VOLTAGE listed on the nameplate.
1
3
5
6
7
4
2
POWER CORD CONNECTION
DIRECT CONNECTION
L1
L2
L1
L2
INTERMEDIATE 
SHUT-OFF BOX 
(may or may not 
be fused)
POWER SUPPLY
POWER SUPPLY
INTERMEDIATE 
FUSE BOX (may 
be omitted if 
service entrance 
box is fused)
WALL 
RECEPTACLE
A typical 
30-Amp 
Three-Wire 
Receptacle 
NEMA Type 
10-30R
120 ± 12
V.A.C.
120 ± 12
V.A.C.
240 ± 12
V.A.C.
NOTE: Use COPPER WIRE only. 
Shorter than 15 ft. (4.5 m) – use 10 AWG
Longer than 15 ft. (4.5 m) – use 8 AWG
D695I
D696I