Installation Instructions
13
M412060
Individual Exhaust
Collector Duct
Figure 1
VERTICAL EXHAUST INSTALLATION
HORIZONTAL EXHAUST INSTALLATION
180° 
Sweep Elbow
No Screen
or Cap
2 in (5.1 cm) 
Minimum 
Clearance
30 in (76.2 cm) 
Minimum 
Clearance
0 in 
Clearance 
Permitted 
for First 
4 in 
(10.2 cm)
12 in (30.5 cm) 
Minimum 
Clearance
0 in Clearance 
Permitted 
for First 
4 in (10.2 cm)
12 in (30.5 cm) 
Minimum 
Clearance
2 in (5.1 cm) 
Minimum 
Clearance
No
Screen 
Or
Cap
Wall
NOTE: Maximum length 
of exhaust duct is 14 
feet (4.3 meters).
NOTE: Maximum length 
of exhaust duct is 14 
feet (4.3 meters).
Clearance permitted to combustible material
36 in (91.4 cm) recommended for maintenance purposes 
24 in (61.0 cm) minimum
Wall
TMB2153N
30 in (76.2 cm) 
Minimum 
Clearance
Figure 2
2 in 
(5.1 cm) 
Minimum 
Clearance
30 in (76.2 cm) 
Minimum Clearance
2 in (5.1 cm) Minimum Clearance
2 in (5.1 cm) 
Minimum 
Clearance
No Screen
or Cap
Wall
Air Out
Inspection or 
Cleanout
Cover
31.62 in
(80.3 cm)
L Dia
K Dia J Dia
I Dia H Dia G Dia F Dia E Dia D Dia C Dia B Dia
A Dia
Ceiling
180° 
Sweep Elbow
NOTE: This collector duct is sized for individually 
ducted units as shown. Refer to Figure 1
.
Where the exhaust duct pierces the wall or ceiling, an 
opening having a diameter four inches larger than the 
diameter of the exhaust duct shall be provided, and the 
exhaust duct centered within the opening.
Duct 
Station
Min. Diameter 
for Individual 
Exhaust
Duct 
Station
Min. Diameter 
for Individual 
Exhaust
A
 7.00 in (17.8 cm)
G
19.00 in (48.3 cm)
B
10.00 in (25.4 cm)
H
20.00 in (50.8 cm)
C
12.00 in (30.5 cm)
I
22.00 in (55.9 cm)
D
14.00 in (35.6 cm)
J
23.00 in (58.4 cm)
E
16.00 in (40.6 cm)
K
24.00 in (61.0 cm)
F
18.00 in (45.7 cm)
L
25.00 in (63.5 cm)
TMB2154N