ELECTRICAL REQUIREMENTS 
For 28" wide Tumblers
NOTE: Minimum wire sizes are obtained from Canadian Electrical Code and are intended for use as a guideline 
only. Electrical connections should be made only by a qualified electrical contractor in accordance with all 
applicable local and national requirements.
NOTE: DO NOT use aluminum wire.
Table 4
Table 5
Table 6
Heat Source
Electrical Specs
Wires Required and Terminal Block Connections
Gas
120/60/1
L1, Neutral, and ground
Gas
208-240/60/1
L1, L2, Neutral, and ground
Gas
240/50/1
L1, Neutral, and ground
Gas
120/50/1
L1, Neutral, and ground
Electric
208/60/1
L1, L2, and ground
Electric
240/60/1
L1, L2, and ground
Electric
240/50/1
L1, Neutral, and ground
Electric
208/60/3
L1, L2, and ground
Electric
240/50/3
L1, L2, L3, and ground
Electric
240/60/3
L1, L2, L3, and ground
Electric
380/50/3
L1, L2, L3, Neutral, and ground
Electric
415/50/3
L1, L2, L3, Neutral, and ground
Electric
480/60/3
L1, L2, L3, and ground
ELECTRIC DRYING TUMBLERS
208V 
60 HZ 
1 PH
240V 
60 HZ 
1 PH
208V 
60 HZ 
3 PH
240V 
60 HZ 
3 PH
480V 
60 HZ 
3 PH
240V 
50 HZ 
1 PH
240V 
50 HZ 
3 PH
380V 
50 HZ 
3 PH
415V 
50 HZ 
3 PH
Amp Rating
104 AMP 92 AMP 62 AMP 55 AMP 27 AMP 91 AMP 55 AMP 34 AMP 31 AMP
Circuit Breaker
125 AMP 100 AMP 70 AMP 60 AMP 30 AMP 100 AMP 60 AMP 40 AMP 35 AMP
Poles
2
2
3
3
3
2
3
3
3
Minimum Wire Size 
Per Canadian Elec. 
Code C22.1
1 AWG
2 AWG
4 AWG
6 AWG
10 AWG
2 AWG
6 AWG
8 AWG
8 AWG
GAS DRYING TUMBLERS
120V 1 Phase 
60 Hz.
208/240V 1 Phase 
60 Hz.
240V 1 Phase 
50 Hz.
120V 1 Phase 
30 Hz.
Minimum Wire Size Per 
Canadian Elec. Code C22.1
14 AWG
16 AWG
16 AWG
14 AWG
Disconnect Switch
15 AMP
USE CIRCUIT BREAKER ONLY
Fusetron
15 AMP
Circuit Breaker
15 AMP
15 AMP
15 AMP
15 AMP
No. of Poles
1
2
2
2