• Collector Venting
While it is preferable to exhaust tumblers individually 
to the outdoors, a main collector duct may be used if it 
is sized accordingly. Refer to Figure 5.  Thi
illustration indicates minimum diameters, and should 
be increased if the collector length exceeds 20 feet 
(6.1 m).  The collector duct may be rectangular in cross 
section, as long as the area is not reduced.  Provisions 
should be made for lint removal and cleaning of the 
collector duct.
The collector duct must be tapered. Refer to Figure 5.  
The individual tumbler ducts must enter the collector 
duct at a 45° angle in the direction of airflow.  Never 
connect a tumbler duct at a 90° angle to the collector 
duct.  Doing so will cause excessive back pressure, 
resulting in poor performance.  Never connect two 
tumbler exhaust ducts directly across from each 
other at the point of entry to the collector duct.
The collector system must be designed so the static 
back pressure measured 12 inches (30.5 cm) from the 
exhaust thimble does not exceed the maximum 
allowable pressure specified on the installation sticker 
on the rear of the tumbler.  This must be measured with 
all tumblers running that are vented into the collector.
MAKE-UP AIR
A tumbler is forced air exhausted and requires provisions 
for make-up air to replace the air exhausted by the 
tumbler. 
IMPORTANT: Do not obstruct the flow of 
combustion and ventilation air.
Recommended make-up air opening to the outside is 
144 inches
2
 (928 cm
2
).
At a minimum, the National Fuel Gas Code requires 
tumblers to have at least one square inch (6.5 sq. cm) 
of opening for every 1000 BTU/hr. of input rating for 
proper combustion.
Example: A tumbler with a rated input of 120,000 
BTU/hr. requires 120 square inches of free 
opening.
The additional opening recomended by the 
manufacturer is required for optimum drying and 
reliability.
Protective louvers in the opening to the outdoors can 
reduce air movement by approximately 40 percent.  The 
opening must compensate for the area taken up by the 
louvers.
The make-up air openings for a room containing 
tumbler(s) and/or gas fired hot water heater or other 
gravity vented appliances must be increased sufficiently 
to prevent downdrafts in any of the vents when all 
tumblers are in operation.  Do not locate gravity vented 
appliances between tumbler(s) and make-up air 
openings.  If it is necessary to duct make-up air to the 
tumbler(s), increase the area of the duct work by 25 
percent to compensate for any restriction in air 
movement.