GE 60-960-95 User Manual

Page of 104
Concord Ultra
12
Note  
The Two-Wire Smoke set-
ting (in program mode) must 
be off when using 4-wire 
smoke detectors. See 
ONBOARD
 
OPTIONS
INPUTS
 
in the section “Programming 
the Panel” for complete 
details.
Figure 8. Wiring Smoke Detectors
Connecting 4-Wire Smoke Detectors
Zone input 8 can be used with 4-wire smoke detectors that latch and remain in the alarm state 
until power is removed, then restored to the detector. The panel provides this power interruption 
from terminal 23 (2-wire smoke power +), provided that zone 8 is learned into sensor group 26 
(fire).
Note  
Zone 8 must be learned into 
sensor group 26 (fire) for 
connected smoke detectors 
to reset after canceling a fire 
alarm.
Table 5 describes the minimum available panel power. Use only 4-wire smoke detectors that 
operate at these power limits. Connect up to five Sentrol (ESL) model 449AT (part no. 13-360) 
smoke detectors to panel power and zone 8 input as shown in Figure 8. 
Connecting Speakers
Note  
Install all sirens/speakers 
indoors, in a concealed loca-
tion.
The panel provides one siren driver output for intrusion (steady), fire (temporal 3), and auxiliary 
(on-off-on-off) alarm sounds. This output trips only for partition 1 alarms.
The output can drive a single 8-ohm speaker or multiple speaker circuit of 8-ohms or higher (as 
shown in the following speaker wiring diagrams). Compatible speakers are described under 
“Connecting Piezo Sirens”.
To avoid disabling the panel speaker output, do not make speaker connections with the 
panel powered up.
15-Watt Speaker (13-060)
For exterior siren applications. Connect the speaker to the panel as shown in Figure 9.
2 2
2 3
Z O N E
8
+ 1 2 V
2 W   S M K
+
-
+
-
Panel
Terminals
2k Ohm EOL
(Locate at Last Detector)
Resistor 49-454
2-Wire
   
   
 
   
 
   
   
      
 
   
   
   
 
 
   
 
 
 
 
 
                     
   
 
 
 
 
 
 
 
 
 
 
 
 
                     
     
 
 
 
 
 
 
 
2k Ohm EOL
(Locate at Last Detector)
Resistor 49-454
Model
449AT
Model
449AT
4-Wire 
Panel
Terminals
Zone
8
2W SMK
+12V
22
23
Table 5: Panel Minimum Available Power
Min. Voltage/Max. Current Available
8.3 VDC, up to 30 mA total (combined alarm) current
8.1 VDC, up to 40 mA total (combined alarm) current
7.7 VDC, up to 60 mA total (combined alarm) current
7.4 VDC, up to 80 mA total (combined alarm) current
Caution
!