APC NBRK0550 User Manual

Page of 152
63
NetBotz Appliance User’s Guide
Unplugged alert severity. 
Select the severity to be applied to the reported alert from the list. This alert 
severity will be used if the Rack Access Pod is unplugged or no longer responding.
Unplugged alert profile. 
Select the alert profile to use when the Rack Access Pod is unplugged or no 
longer responding.
Configuring the Rack Access Pod sensors
The Rack Access Pod 170 can have two sets of sensors attached to the appliance. Each set consists of 
four components; a door sensor, a handle sensor, a lock sensor, and a card reader sensor.
Select a Rack Access Pod from the Rack Access Pods window and click Sensors. The Sensor 
Configuration
 window displays a Sensors list and a Thresholds list. Select a sensor from the Sensors 
list to display thresholds defined for the sensor in the Thresholds list. 
To modify a sensor:
1. Select the sensor to modify from the Sensors list and click Modify.
2. Enter a label in the Label field. This label can be up to 64 characters, and identifies the sensor in 
the Sensor Data pane, Advanced View interfaces, and in alert notifications.
3. From Sensor Value History, select the amount of time that data reported by this sensor is stored 
on the appliance. The amount of data available on the appliance affects the maximum amount of 
data that can be graphed.
4. Click OK
Threshold configuration
All door, handle, and lock sensors have a default threshold that is generated automatically by Advanced 
View. This threshold provides the typical threshold used for the specific sensor type. Thresholds can be 
customized.
Specific Rack Access thresholds are available for each sensor type. This thresholds are 
explained in detail in “Defining State Thresholds” on page 109.
To enable or modify a sensor threshold:
1. Select a sensor from the Sensor selection list.
2. Select the threshold to enable or modify from the Thresholds selection list. Click Edit....
3. The Edit Threshold window appears.
– To enable the threshold, check Enabled
– To change threshold settings, use the Basic and Advanced controls in the Edit Threshold 
window to set new values. 
4. Click OK.