NetBotz Room Sensor Pod 155 Installation Manual
5
Rear
Item
Description
Sensor ports
Used for connecting APC sensors, third-party dry contact sensors, and 
standard third-party 0-5 V sensors. (See “Additional options” on 
page 3 
for details on APC sensor options.)
Third-party dry contact sensors require the NetBotz Dry Contact Cable 
(NBES0304). Standard third-party 0-5 V sensors require the 
NetBotz 0-5 V Sensor Cable (NBES0305).
A-Link ports
• Left  port  in
• Right  port  out
Used for connecting the NetBotz 155 to a NetBotz Rack Monitor 450,  
NetBotz Room Monitor 455, or NetBotz Rack Monitor 550. Standard 
CAT-5 cabling with straight-through wiring is required. Depending on 
the appliance to which the NetBotz 155 is connected, multiple devices 
may be cascaded along an A-Link bus.
24 VDC input
Provides supplemental power for high-current load configurations. 
Supplemental power is not required for most system configurations. 
See the installation and quick configuration manual included with your 
appliance to determine whether supplemental power is required.