Liebert 50 & 60Hz User Manual

Page of 72
Microprocessor Control
42
3.18 Run Diagnostics
By selecting Run Diagnostics, maintenance personnel can check system inputs, outputs, and conduct 
a test of the microcontroller circuit board from the wall box control. A review of the system inputs and 
the microcontroller test can be done without interrupting normal operation.
Test Outputs
• When this feature is selected, the controller is effectively turned off. When stepping from one load 
to the next, the previous load is automatically turned off. The loads can also be toggled on/off by 
selecting “ENTER”. Once turned on, the output will remain on for five minutes unless toggled off 
or the test outputs function is exited by selecting “MENU/ESC” (Compressor is limited to 15 sec-
onds on to prevent damage.  
The outputs are:
• Main  Fan
• Compr1 (3-ton)
• Compr1 & HGBP1
• Compr2
• Compr2 & HGBP2
• Compr1 & Compr2
• Chill Water/Gly (if present)
• Reheat 1
• Reheat 2
• SCR Reheats (if present)
• Humidifier
• Common Alarm
Test Inputs
With the unit on and the fan running, the input states may be displayed for the following devices:
• Input  Power
• High Water in Pan
• High Head Comp1
• High Head Comp2
• Air Sail Switch (requires additional factory-installed components)
• Filter  Clog
• Humidifier Prob.
• Custom Alarm #1
• Custom Alarm #2
• Custom Alarm #3
!
CAUTION
Testing compressor output for more than a few seconds could damage the compressor. To 
eliminate damaging the compressor during testing, DO NOT test compressor output for more 
than a few seconds.
!
CAUTION
Extended unit operation in the test outputs mode for troubleshooting may cause damage to 
unit. DO NOT operate unit in the test outputs mode any longer than is necessary for 
troubleshooting.
NOTE
Fan turned on with all loads.