Enerco HSVFR10LPT User Manual

Page of 16
9
Installation Instructions and Owner’s Manual
Unvented Liquid Propane Fired Room Heater
Figure 12
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections for 
leaks after installing or servicing. Correct all leaks 
at once. 
WARNING: Never use an open flame to check for 
a gas leak. Apply a mixture of liquid soap and water 
to all joints. Bubbles forming show a leak. Correct 
all leaks at once. 
PRESSURE TESTING GAS SUPPLY PIPING 
SYSTEM
High Pressure 
Test pressure in Excess of ½ psig (3.5kPa)
1.  Disconnect appliance with its appliance main 
gas valve (control valve) and equipment shutoff 
valve from gas supply piping system. Pressures 
in excess of ½ psig will damage heater regula-
tor.
2.  Cap off open end of gas pipe where equipment 
shutoff valve was connected.
3.  Pressurize supply piping system by either using 
compressed air or opening main gas valve on 
or near gas meter.
4.  Check all connections and joints in gas supply 
piping system. Apply mixture of liquid soap and 
water to gas joints. Bubbles forming show a 
leak.
5.  Correct all leaks at once.
6.  Depressurize and relieve pressure in supply 
piping system.
7.  Reconnect heater and equipment shutoff valve 
to gas supply. 
8.  Reconnected fittings must be checked for leaks 
in next section. 
Low Pressure
Test Pressure Equal To or Less Than ½ psig (3.5 
kPa)
1.  Close equipment shutoff valve (see figure 13).
2.  Pressurize supply piping system by either using 
compressed air or opening propne/LP supply 
valve.
3.  Check all joints from the propane/LP supply 
valve to equipment shutoff valve (see figure 
14). Apply mixture of liquid soap and water to 
gas joints. Bubbles forming show a leak.
4.  Correct all leaks at once.
5.  Depressurize and relieve pressure from supply 
piping system.
Pressure Testing Heater Gas Connections:
1.  Make sure that the heater supply piping sys-
tem is connected and has been leak tested as 
described above.
2.  Make sure control knob of heater is in OFF 
position.
Figure 13
3.  Open equipment shutoff valve (see figure 13). 
4.  Open propane/LP supply valve.
5.  Check all joints from equipment shutoff valve 
to control valve (see figure 14). Apply mixture 
of liquid soap and water to gas joints. Bubbles 
forming show a leak.
Figure 14
6.  Correct all leaks at once.
7.  Light heater (see Operating Your Heater, page 
page 10.
Equipment 
Shutoff Valve
Open
Closed
Pressure 
Regulator
Heater 
Cabinet
Ground Joint Union
Equipment 
Shutoff Valve
From LP tank 
(11” W.C. to 14” 
W.C. Pressure)
Tee Joint
1/8” NPT Plug Tap
Cap
Pipe Nipple
Tee Joint
3/8” NPT Pipe Nipple
Sediment 
Trap
Test Gauge 
Connection
Reducer Bushing 
to 1/8” NPT
3” Minimum
Control Valve
Equipment 
Shutoff Valve
To regulated propane 
source