Wall Mounted Control Humidistat:
Wall-mounted humidistats are usually installed 4 ft. to 5 ft. above floor level. Often, the best location is
beside a thermostat that controls temperature in the same space that is to be humidified, if that loca-
tion meets the following criteria:
•   The control humidistat should be located where it will be exposed to the average air condition of the
space to be humidified.
•   Avoid areas of restricted air circulation, or locations where the sensor will be subjected to air drafts,
localized heat, or moisture sources.
•   Locations near coffee machines, computer blower outlets, doors to other rooms, or windows that
can be opened are not suitable.
10
Modulating
High Limit
Sensor
6 - 10 Ft.
Outdoor
Temperature 
Sensor
Air Flow Switch
Humidifier
Location
Main Humidity Sensor
Humidifier 
Connections
Outside Air
Safety
High Limit
Humidistat
(optional)
Figure 10-1