Sterling A0552321 User Manual

Page of 36
Pump Tanks 
Chapter 6: Appendix 
21 of 36 
 
 
6-3  Drawings and Specifications 
Cooling Tower Water Pump Tanks 
American Standards 
 
 Maximum 
 
 Return 
 
Tank 
weight 
 tower 
tons 
c Capacity Maximum
water 
overflow 
Dimensions (less 
pumps) 
Model Single 
Dual 
gallons 
pumps/ 
connections
inches 
pounds 
number well 
well 
Overflow 
Operating
ledge  Inches  L W H Shipping 
Operating
CT140 (D) 
25 
13 
125 
100 
3” NPT 
72 
36 
40 
600 
1,800 
PT390 (D) 
d
 
78 39  390 
350 
ℜ 
5” CLMP 
95 56  64 
500 
3,500 
CT480 (D) 
90 
45 
450 
360 
4” FLG 
102 
49.5
52 
2,000 
6,000 
CT720 (D) 
135 
68 
675 
540 
4” FLG 
114 
73.5
52 
2,600 
8,600 
CT1080 (D) 
206 
103 
1,030 
900 
6” FLG 
114 
73.5
77 
3,400 
12,400 
CT1620 (D) 
310 
155 
1,550 
1,345 
6” FLG 
138 
73.5
77 
4,000 
17,500 
CT2040 (D) 
382 
191 
1,910 
1,685 
6” FLG 
150 
91 
78 
5,000 
22,100 
CT2700 (D) 
509 
225 
2,545 
2,245 
6” FLG 
150  121 
78 
6,000 
28,500 
CT3670 (D) 
698 
349 
3,490 
3,140 
6” FLG 
162  121 
90 
7,000 
37,600 
CT5130 (D) 
978 
489 
4,890 
4,400 
ℜ  
8” FLG 
162 169 
92 
7,800 
50,700 
CT6285 (D) 
1,257 
629 
6,285 
5,655 
ℜ 
10” FLG 
162 217 
94 
14,700 
69,100 
c   Based on three (3) gpm per ton and towers being within 25 feet of the tank. 
d  “P” signifies molded polyethylene tank. 
ℜ  PT390 = 6” CLMP, CT5130 = 6” FLG, CT6285 = 8” FLG overflow connections only. 
 
Metric Standards 
 
 Maximum 
 
 
Return 
 
Tank 
weight 
 tower 
cooling 
c Capacity 
Maximum
water 
overflow 
Dimensions (less 
pumps) 
Model Single Dual 
liters 
pumps/ 
connections
cm 
Kg 
number well  well 
Overflow 
Operating
ledge mm L 
Shipping Operating
CT140 
(D) 94,615 
49,200 
473  378 3  76 
mm 
183
91 
102 
273 817 
PT390 (D) 
d
 
295,200 147,599 1,476 
1,325 
ℜ 127 mm  241 142 162 
227 
1,588 
CT480 (D) 
340,619 
170,303 
1,703 
1,362 
102 mm 
259
126  132 
908 
2,722 
CT720 (D) 
510,921 
257,353 
2,555 
2,044 
102 mm 
289
187  132 
1,180 
3,901 
CT1080 (D) 
779,628 
389,814 
3,899 
3,407 
152 mm 
289
187  195 
1,543 
5,625 
CT1620 (D) 
1,173,195 
586,613 
5,867 
5,091 
152 mm 
350
187  195 
1,815 
7,938 
CT2040 (D) 
1,445,717 
722,859 
7,229 
6,378 
152 mm 
381
231  198 
2,268 
10,025 
CT2700 (D) 
1,926,361 
965,073 
9,633 
8,497 
152 mm 
381
307  198 
2,722 
12,928 
CT3670 (D) 
2,641,651 
1,320,825 
13,209 
11,885 
152 mm 
411
307  229 
3,176 
17,056 
CT5130 (D) 
3,701,339 
1,850,669 
18,509 
16,654 
ℜ 203 mm  411 429 234  3,539 
22,998 
CT6285 (D) 
4,757,242 
2,380,513 
23,789 
21,404 
ℜ 254 mm  411 551 239  6,668 
31,344 
c   In Kcal/hr, calculated for cooling tower water, based on 3 lpm per 1,000 Kcal/hr and towers being within eight (8) meters of the 
tank. 
d  “P” signifies molded polyethylene tank. 
ℜ  PT390 = 152mm, CT5130 = 152mm, CT6285 = 203mm overflow connections only. 
Top View
Front View
Side View
(P2 Pump Shown Only For Clarity)