APC ACRD101 User Manual

Page of 56
InRow RD 10 kW Air Cooled Operation and Maintenance
44
Troubleshooting
Problem Possible 
Cause
Corrective 
Action
Controls erratic or 
inoperative
• Inlet temperature to cooling 
unit is higher than rated 
maximum temperature
• Reduce the load or add additional cooling equipment.
Fans fail to start
• Power supplies are not 
operating properly
• Confirm that the power supplies are seated properly and fully 
engaged. This is indicated by a green LED.
• Confirm that the cooling unit is plugged in and is receiving 
power. 
• Failed power supply
• Replace the power supply if the LED is red. 
• Cooling unit shutd own due to 
an external command
• Temporarily remove the user contact cable, if it is connected.
• Single fan fails to start
• Verify that the fan circuit breaker is 
O
N
.
Cooling unit cannot 
obtain setpoint
• Improper placement of remote 
temperature sensor
• Verify that the remote temperature sensor is properly located 
in the cold aisle.
• Dirty filter
• Clean the filter.
• Dirty coil
• Clean the coil.
• Application error
• For assistance, contact APC at a number on the back cover of 
this manual.
• Heat load is too far away
• Place the cooling unit closer to the heat load.
Water carryover
• Improper fan speed selected 
• RACS and HACS modes only. Select the next highest fan 
speed setting. For example, change the fan speed setting from 
Low to Med/Low. 
Temperature control 
not tight enough
• Improper placement of remote 
temperature sensor
• Verify that the remote temperature sensor is properly located 
in the cold aisle.
Water on outside of 
cooling unit
• Condensate drain hose is not 
connected or not properly 
routed outside the cooling unit
• Verify that the condensate drain hose is properly connected to 
the pump and properly routed outside of the cooling unit.
• Verify that the condensate drain line does not exceed 4.9 
meters (16 feet) lift and 15.4 meters (50.0 feet) horizontal run.
• Leak in piping system
• Locate and repair the leak.
• Cooling unit not leveled 
properly
• Adjust the leveling feet of the cooling unit.
• Damaged piping insulation
• Identify damaged area and repair the insulation.
Display interface not 
operational but 
cooling unit operates
• Display interface not 
connected properly
• Verify that the display interface cable is connected properly.
Incorrect air pressure • False filter clogs
• Verify that the ends of the clear plastic air tubes are not 
obstructed.
• Verify that the clear plastic air tubes are connected to the 
controller.
• Verify that the clear plastic air tubes are not pinched.
Alarms do not show 
up on monitoring 
equipment (Customer 
Output Contact)
• External monitoring equipment 
is not receiving power or is not 
functioning properly
• Confirm that power, if required, is being supplied to the 
external equipment.
• If the cooling unit (+12 V or +24 V) is providing power to the 
external equipment, verify that the external equipment is 
<50 mA.
• Test the external equipment by bypassing the output contact.
• Verify Customer Output Contact settings. See “Contacts” on