Operation
NetworkAIR Rack Air Removal Unit Installation
11
To check operation of the unit:
5. Apply power to the fans by turning the fan speed selector from the OFF position to one of the 
four exhaust temperature settings.
6. Make sure the fans are moving.
7. Turn off the power to the unit.
How to set the fans based on wattage
Determine the wattage of your equipment and set the fan speed selector to the corresponding kW 
setting. 
\
Temperature override
The kW settings on the fan speed selector run the fans at a constant speed, while the exhaust 
temperature settings adjust the fan speed depending on the exhaust temperature of the equipment in 
the rack. The Rack Air Removal Unit is equipped with a temperature override that protects the 
equipment in the rack while the unit is in kW mode. If the unit is in kW mode, and the exhaust 
temperature rises above 40.5° C (105° F) (the override setpoint), the unit increases the fan speed to 
remove excess heat from the rack.
Note
If no air is flowing from the Rack Air Removal Unit, check the power connection.
Warning
Setting the kW setpoint too low could damage the equipment in the enclosure. If 
the amount of kW in your enclosure falls between two of the numbers on the 
setpoint dial, choose the higher number or set based on exhaust temperature.
Note
When the temperature override is enabled and the temperature in the rack rises above 
40.5° C (105° F), the Rack Air Removal Unit will automatically increase the fan speed 
to bring the temperature below 40.5° C (105° F).
Warning
When in kW mode and using a UPS that is 3000VA or lower, disable the 
temperature override to prevent the power draw from exceeding the limitations 
of the UPS.
The UPS should not be loaded above 80% when using the Rack Air Removal 
Unit.