Thermo Products CMC1-75DV3N User Manual

Page of 65
All installations and services must be performed by qualified service personnel. 
gas flame. Should acid compounds form in your furnace, it may reduce the 
life of the furnace.
  
 
 
H.  Direct Venting Through a Sidewall 
 
 
1.  Vent And Combustion Air Pipes 
 
Vent and combustion air pipes may pass through a maximum wall thickness 
of 18 inches. The     minimum wall thickness is 2 inches.  Referring to Figure 
7, the maximum distance from the outer wall to the center of the elbow is 12 
inches. 
Figure 7: Proper Direct Vent Terminations (RH & LH views) and Vent 
Termination Only w/o Outside Combustion Air Intake (RH view) 
NOTICE:  If exterior sidewall building materials are subject to degradation 
from contact with flue gases or moisture, a minimum 24-inch diameter shield 
shall be fabricated from stainless steel or UV-resistant plastic sheet. The 
protective shield shall be installed around the vent pipe on the outside wall. 
 
2.  Exhaust Vent Termination Elbow 
 
The exhaust vent termination elbow shall be installed in accordance with 
these instructions and any applicable local codes. Refer to Figures 7 and 8 for 
typical examples of proper terminations. 
   
a.  The exhaust vent termination must be installed in the same 
atmospheric pressure zone (i.e. on the same wall) as the air intake 
termination.  
 
 
24