All installations and services must be performed by qualified service personnel. 
IMPORTANT:    The room thermostat should be installed 4 to 5 feet above 
the floor on an interior wall which is relatively free from direct sources of 
heat (sunlight or supply airflow) or exposure to cold (drafts from open 
windows and doors).  The nominal anticipator setting is 0.8 amperes, for 
the CMA/CMC (refer to the thermostat literature for additional information). 
 
Four-conductor thermostat wire is recommended for 24 VAC, low-voltage, 
control circuit wiring.  However, only 2 wires are required for the furnace (a 
heating application only). 
 
 
 
Electrical Wire 
Diameter 
Maximum Recommended 
Thermostat Wire Length 
(AWG) 
(Feet) 
24 
55 
22 
90 
20 
140 
18 
225 
 
Once the furnace is installed, check the thermostat anticipator for proper 
nominal setting. 
 
1.  Connect a multimeter, capable of reading milliamps (mA), in series 
with the low voltage wires to the thermostat.  
2.  Increase the thermostat setting, or create a “call for heat”.  
3.  Read the value of the thermostat current, in milliamps.  
4.  Adjust the heat anticipator of the thermostat to the value read by the 
 
multimeter. 
 
If the heat anticipator is set too high, the furnace may delay activation of a 
heating cycle for too long.  If the heat anticipator is set too low, the furnace 
may cycle too frequently.  Either condition may not provide optimal 
comfort to the homeowner. 
 
 
     
 
 
 
 
 
 
 
 