5-3   Alarms 
Use the Alarm History screen to monitor system alarms. From the Main Menu screen, press 
the Alarms button to access the Alarm History screen. The three most recent alarms appear at 
the top of the Alarm History screen. Use the DOWN and UP buttons to scroll through the 
alarms.  
    (
Alarm History Screen)
 
                                        
 
 
5-4   Alarm Descriptions 
 
Alarm 
Comment 
Alarm 
Description 
Alarm 
Effect 
VALVE 
POSITION 
The Main Air Valve did not maintain 
position. 
Possible Motor or Limit Switch Failure. 
Immediate 
Shut Down  
VALVE 
MTR 
OVERRIDE 
The Main Air Valve did not find 
position. 
Possible Motor or Limit Switch Failure. 
Immediate 
Shut Down 
VALVE  
MOTOR FAIL 
The Main Air Valves expected and actual 
positions do not match. 
Possible Motor or Limit Switch Failure. 
Immediate 
Shut Down 
PROCESS  
SENSOR FAIL 
The process supply air temperature 
thermocouple is out of range. 
Possible thermocouple failure. 
Process 
Shut Down 
REGEN  
SENSOR FAIL 
The regeneration air temperature 
thermocouple is out of range. 
Possible thermocouple failure. 
Regeneration 
Shut Down 
PROCESS  
HIGH TEMP 
Process air temperature deviation is 
above high limit value. 
Possible solid state relay failure. 
Process 
Shut Down 
PROCESS  
LOW TEMP 
Process air temperature deviation is 
below low limit value. 
Possible heater failure. 
Alert Only 
PROCESS  
LOOP BREAK 
Process air temperature control loop is 
unable to maintain the process air 
temperature set point. 
Possible Missing thermocouple, Failed 
heater, Failed solid state relay. 
Process 
Shut Down 
REGEN  
HIGH TEMP 
Regeneration air temperature deviation is 
above high limit value. 
Regeneration 
Shut Down