Unit not providing ventilation. Ventilation timer not operating 
correctly. 
1. If timer is not functioning correctly reset timer and reprogram. 
2. Check control wire connections (check connections at fresh 
air damper also). 
3. Defective fresh air damper. 
4.Defective fan switch. 
Unit removes some water, but not as much as expected. 
1. Air temperature and/or humidity have dropped. 
2.  Humidity meter and or thermometer used are  
out of calibration.
3. Unit has entered defrost cycle. 
4. Air filter dirty. 
5. Defective defrost thermostat. 
6. Low refrigerant charge. 
7. Air leak such as loose cover or ducting leaks. 
8. Defective compressor. 
9. Restrictive ducting. 
10.Optional Condensate Pump Safety Switch open. 
Unit Test to determine problem: 
1. Detach field control wiring connections from main unit. 
2.  Connect the yellow and green pigtails from the main unit 
together; only the fan should run. Disconnect the wires. 
3.  Connect the yellow and blue pigtails from the main unit 
together; the compressor and fan should run. 
4.  If these tests work, the main unit is working properly. You 
should check the control panel and field control wiring for 
problems next. 
5.  Remove the control panel from the mounting box and detach 
it from the field installed control wiring. Connect the blue, 
yellow, and green wires from the control panel directly to the 
corresponding colored pigtails on the main unit. Leave the 
violet, white and red wires disconnected! 
6.  Turn on the fan switch; the fan should run. Turn off the fan 
switch. 
7.  Turn on the humidity control; the compressor and fan should 
run. 
8.  If these tests work, the problem is most likely in the field 
control wiring. 
11.3 Refrigerant Charging 
If the refrigerant charge is lost due to service or a leak, a new 
charge must be accurately weighed in. If any of the old charge is 
left in the system, it must be recovered before weighing in the new 
charge. Refer to the unit nameplate for the correct charge weight 
and refrigerant type. 
11.4 Compressor/Capacitor Replacement 
This compressor is equipped with a two terminal external overload 
and a run capacitor, but no start capacitor or relay. 
CAUTION
 
CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power must 
be present to perform some tests. These tests should be 
performed by a qualified service person. 
11.5 Electric Ventilation Damper 
The electric ventilation damper is controlled by the ventilation timer. 
The damper will open when the ventilation timer is activated to 
allow fresh air into the structure through the 6" diameter fresh air 
inlet duct. The electric ventilation damper will remain closed when 
the ventilation timer is not activated to prevent over-ventilating 
the structure when the unit is dehumidifying or recirculating the 
indoor air. The electric ventilation timer operates on 24 Vac from the 
control circuit. DO NOT connect high voltage to the damper motor 
or damage to the motor may result. DO NOT force the blade of the 
damper by hand or damage to the damper motor may result. 
The damper opens in one direction only. The damper rotates very 
slowly, allow sufficient time for the damper to cycle. The damper 
will take approximately one minute to cycle from closed to open or 
from open to closed. 
If the electric ventilation damper fails to operate: 
1.  Check that the wiring is correct and that voltage is present at 
the damper motor. 
2.  Check for any obstruction inside the damper. If the electric 
ventilation damper fails to operate after performing these 
checks, it must be replaced. 
11.6 Condensate Pump Kit 
An optional condensate pump kit is available from the factory for 
use with the UA-90H. Condensate is automatically pumped to a 
remote location when the water level in the pump’s reservoir rises 
to close the float switch. The pump also contains a safety float 
switch. The white leads from this switch extend from beneath the 
pump cover. This switch should be installed in series with the field 
wire that connects the blue (#5) lead from the UA-90H to the blue 
(#5) lead on the control panel. If the pump fails, this switch opens 
the compressor control circuit and stops water production before 
the reservoir overflows. The UA-90H will continue to ventilate or 
circulate air as normal, but will not dehumidify until this switch 
closes.  See following pages for more information.