American Aldes DH-100V User Manual

Page of 10
 
DH-100V
 
HIGH EFFICIENCY DEHUMIDIFIER 
 
INSTALLATION 
OPERATION 
MAINTENANCE  
972 DH 09-12
  A L D E S   D H - 1 0 0 V  
Installation, Operation & Service Instructions
 
 
 
Table of Contents
 
1. Specifications....................................................... 1 
2. Installation ............................................................ 1 
 2.1 
Location ............................................................ 1 
   
2.1A In humid area, no ducting. .......................... 1 
  2.1B 
In humid area, duct inlet and/or outlet
. .......... 1 
    2.1C In remote area, duct inlet & outlet............... 2 
    2.1D In remote area, duct outlet only. ................. 2 
    2.1E In remote area, duct inlet only. ................... 2 
 2.2 Electrical Requirements .................................... 2 
 2.3 Condensate Removal........................................ 2 
 2.4 Ducting .............................................................. 2 
  2.4A 
Optional Ducting ........................................ 2 
    2.4B Ducting for Dehumidification ....................... 2 
  2.4C 
Ducting 
for Fresh Air................................... 3 
3. Operation .............................................................. 3 
  3.1 Humidity Control Adjustment............................. 3 
 3.2 Fan Switch......................................................... 3 
4. Maintenance ......................................................... 3 
 4.1 Air Filter ............................................................. 3 
 4.2 Blower Oiling ..................................................... 3 
5. Service .................................................................. 4 
 5.1 Warranty ............................................................ 4 
 5.2 Technical description ........................................ 4 
 5.3 Troubleshooting................................................. 4 
 5.4 Refrigerant Charging ......................................... 5 
 5.5 Blower Replacement ......................................... 5 
 5.6 Compressor/Capacitor Replacement................ 5 
    5.6A Checking Compressor Motor Circuits ......... 5 
    5.6B Replacing a Burned Out Compressor......... 5 
  5.6C 
Replacing a Compressor- Nonburn Out .........
 5.7 Humidity Control................................................ 6 
 5.8 Defrost Thermostat............................................ 6 
  5.9 Condensate Pump............................................. 6 
6. Wiring Diagrams .................................................. 7 
7. Service Parts List................................................. 8 
8. Warranty................................................................ 9 
9. Service Notes ..................................................... 10 
 
Serial No.________________________________  
Purchase Date____________________________  
Dealer's Name____________________________
 
Read the installation, operation and maintenance 
instructions carefully before installing and using this unit. 
Proper adherence to these instructions is essential to 
obtain maximum benefit from your DH-100V 
dehumidifier. 
1 Specifications
 
Model:  DH-100V Dehumidifier 
Electrical: 110-120 VAC, 6.8 Amps, grounded 
Capacity: 100 pints/day @ 80
°F, 60% RH 
Operating Temp. Range: 53
°F min, 105°F max 
Air Flow:  255 CFM without external ducting 
 
170 CFM @ 0.15 in.wg. external static 
Refrigerant Charge: 1 lbs., 14oz. R-22 
Optional Duct connections: 8" round inlet & outlet 
Size (w/o duct collars): 
20" long x 17" wide x 36" high 
Weight: 103 lbs. 
2 Installation
 
2.1 Location
 
The DH-100V can be installed in a variety of locations to 
meet the owner's needs as listed below. In all cases, 
keep the following cautions in mind: 
•  It is designed to be installed INDOORS ONLY
•  If used near a pool or spa, be certain there is NO 
chance the unit could roll into the water or be 
splashed and that it is plugged into a GROUND 
FAULT INTERRUPTER. 
 DO 
NOT use the DH-100V as a bench or table. 
•  Avoid discharging the air directly at people, 
especially in pool areas. 
2.1A In humid area, no ducting
The simplest installation is to place the DH-100V in the 
humid area with no ducting. The air inlet on top & outlet 
on the side must be at least 1' from walls and other 
obstructions to air flow. 
2.1B In humid area, duct inlet and/or outlet
If the humid area is very large or has high ceilings, 
dehumidification can be improved by adding an inlet 
and/or outlet duct to circulate and destratify stagnant 
areas. For a large area, add inlet or outlet ducting to 
create flow across the area's greatest length. 
For areas with ceilings higher than 12', use an inlet duct 
to draw warm, moist air from near the ceiling. See 
section 2.4 for attaching duct collars & ducting.