Grizzly G0572 User Manual

Page of 32
G0572 Hanging Air Filter with Remote
-13-
Figure 5. Poor air circulation. Placed too close 
to the wall, the air circulation short cycles, leav-
ing much of the room unfiltered.
Filter
The  G0572  Hanging  Air  Filter  with  Remote  will 
recirculate  the  entire  volume  of  air  in  a  room 
measuring 25' X 25' X 8' approximately 12 times 
in one hour. We recommend that the volume of 
air in your room be recirculated at least 6-8 times 
every hour. 
To  calculate  the  recirculating  rate  for  your 
shop space:
Step 1. Use the formula below to calculate how 
long  it  takes  to  circulate  all  the  volume  of  air  in 
your  shop.  The  rate  of  air  movement  for  the  air 
filter is 1044 cubic feet per minute.
W X L X H  = Minutes for circulating 1 time
    1044
Example:  25' X 25' X 8'  = 5000  = 4.79 Minutes 
    
       1044 
     1044
Step 2. Calculate how many times per hour the 
volume  is  recirculated  through  the  hanging  air 
filter  by  dividing  60  minutes  by  the  circulating 
time from 
Step 1. The result is listed as times per 
hour.
Example:     60      = 12.52 Times per Hour
 
       4.79
Filter Capacity
Below  is  a  list  of  things  to  keep  in  mind  when 
selecting a spot for the air filter:
• 
Study your shop layout and try to determine 
the  best  location  for  the  hanging  air  filter. 
Air flow that is obstructed will cause a short 
cycle effect, producing unsatisfactory results. 
There  must  be  a  clearance  of  at  least  12" 
from any obstructions in front and back of the 
unit.
• 
Try to place the air filter in front of high dust 
producers like sanders or near areas where 
sanding will take place.
• 
Do  not  place  the  hanging  air  filter  where 
garage  doors  may  pass  closely  or  where  it 
may  impede  transport  or  movement  of  any 
other object.
• 
Try to place the unit where it is easy to access 
for turning it on, cleaning and maintenance.
Figure 5 shows an example of poor air circulation, 
where the air filter is placed too close to obstruc-
tions. In this situation, the velocity of the air is lost 
and circulation is diminished.