Emerson Process Management 3422 User Manual
156
AGA 8 Setup page
Section 5: Startup and meter configuration
Reference, Installation, and Operations Manual
June 2013
3-9000-743 Rev S
1.
From the
Field Setup Wizard - AGA 8 Page
, choose the desired settings:
•
AGA8 calculations to be performed:
—
Internally (by meter)
—
Base temperature
—
Base pressure
—
Base absolute pressure
—
Externally
—
Fixed
—
Live
Table 5-20 Field Setup Wizard - AGA 8 Setup
AGA8 method
Configuration Parameters
Gross Method 1
Specific gravity: Relative density; used as input to the AGA8 Gross Methods 1 and 2 calculations
•
Reference temperature - for the specific gravity
•
Reference pressure - for specific gravity
•
CO2 - Mole percentage CO2 in the natural gas mixture
•
Hydrogen - Mole percentage of hydrogen
•
CO - Mole percentage of carbon monoxide
Volumetric gross heating
•
Molar density ref temperature: Reference temperature for the molar density; used as
input to the AGA8 Gross Method 1 calculation
•
Molar density ref pressure: Reference pressure for the molar density; used as input to the
AGA8 Gross Method 1 calculation
Gross Method 2
Specific gravity: Relative density; used as input to the AGA8 Gross Methods 1 and 2 calculations
•
Reference temperature - for the specific gravity
•
Reference pressure - for the specific gravity
•
CO2 - Mole percentage CO2 in the natural gas mixture
•
Hydrogen - Mole percentage of hydrogen
•
CO - Mole percentage of carbon monoxide
•
Nitrogen - Mole percentage of nitrogen in the natural gas mixture (AGA8 Gross Method 2
calculation)
AGA8 method
Configuration Parameters
Detail
Enter the amount of each of the 21 gas components as a percentage.
This option is only available in Mark III meters
This option is only available in Mark III meters
•
Gas composition - Select either the Fixed or Live GC.
–
Fixed: Select this option to use the fixed gas composition stored in the meter for all
calculations for which they are required.
–
Live GC: Select this option to use a gas composition collected by the meter from a
gas chromatograph for all calculations for which they are required. This option is
only available for Mark III meters with a valid GCKey
only available for Mark III meters with a valid GCKey
Externally
•
Select if AGA8 calculations are done externally. The calculated values must then be
written to the meter using Daniel MeterLink or a flow computer. The following properties
must be entered. If a flow computer or SCADA system is used to write these values to the
meter, they do not have to be entered at this time.
must be entered. If a flow computer or SCADA system is used to write these values to the
meter, they do not have to be entered at this time.
–
Flow mass density
–
Flow compressibility
–
Base compressibility
Note: Mark II meters - Externally calculating the AGA8 calculations is only available for DFI boards running version 3.40 or later
firmware.
firmware.