Main burner goes
out; pilot stays on.
Pilot flame is not large
enough or not engulfing the
thermopile
-  service or replace Oxygen Depletion Sensor System
- correct piping and/or regulator to provide correct pressure
Thermopile shorting
- clean thermopile connection to the valve. Reconnect.
- replace Oxygen Depletion Sensor System / valve.
Remote wall switch wire is
too long; too much resist-
ance in the system.
-  shorten wire to correct length or wire gauge.
Faulty thermostat or switch.
-    replace.
Pilot burning; no
gas to main
burner; gas knob
is on 'HI'; wall
switch / thermostat
is on.
Themostat or switch is de-
fective.
-  connect a jumper wire across the wall switch terminals; if main
burner lights, replace switch / thermostat.
Main burner orifice is plugged.
-    remove stoppage in orifice.
Faulty valve.
-  replace.
Wall switch wiring is defec-
tive.
-  disconnect wires from valve. Connect a jumper wire across termi-
nals 1 & 3; if the main burner lights, check the wires for defects and
/ or replace wires.
Pilot goes out when
the gas knob is re-
leased.
The gas valve has
an interlock device
which will not allow
the pilot burner to
be lit until the ther-
mocouple has
cooled. Allow ap-
proximately 60
seconds for the
thermocouple to
cool.
System is not correctly
purged.
-  purge the gas line. If a glass door has been installed, ensure that
the door is open or removed prior to purging.
Thermocouple shorting /
faulty.
-  loosen and tighten thermocouple.
-  clean thermocouple and valve connection.
-  replace Oxygen Depletion Sensor System
-  test and replace valve.
Faulty valve.
-  replace.
Out of propane gas.
-  fill the tank.
Pilot flame is not large
enough. (Supply pressure
too low.)
-  service or replace Oxygen Depletion Sensor System
ELECTRODE
PILOT
BURNER
THERMOCOUPLE
THERMOPILE
Pilot will not light.
-  check if pilot can be lit by a match
-  check that the wire is connected to the push button ignitor.
-  check if the push button ignitor needs tightening.
-  replace the wire if the wire insulation is broken or frayed.
-  replace the electrode if the ceramic insulator is cracked or broken.
-  replace the push button ignitor.
 No spark at pilot burner
-  fill the tank.
Out of propane gas
No gas at the pilot burner
-  check that the manual valve is turned on.
-  check the pilot orifice for blockage.
-  replace the valve / Oxygen Depletion Sensor System.
-  call the gas distributor.
Main burner goes
out; pilot goes out.
Insufficient air supply
- open window or door. (Use one of the methods described in ANSI
Z223.1 Section 5.3 or the applicable local code.)
Out of propane gas.
-  fill the tank.
Pilot flame is not large
enough. (Supply pressure
too low.)
-  service or replace Oxygen Depletion Sensor System
- correct piping and / or regulator to provide correct pressure.
TROUBLE SHOOTING GUIDE
SYMPTOM
PROBLEM
TEST  SOLUTION