VenTInG InSTallaTIon InFoRMaTIon
Outside Corner
Inside Corner
Termination Clearances
Termination clearances for buildings with combustible and noncombustible exteriors. 
G =
Combustible 
  6" (152 mm)
Noncombustible 
  2" (51 mm)
F =
Combustible 
  6" (152 mm)
 
Noncombustible 
  2" (51 mm)
G
Balcony - 
with no side wall
M = 
Combustible &
Noncombustible
  12" (305 mm)
M
Balcony - 
with perpendicular side wall
M = 24" (610 mm)
P = 20” (508 mm)
M
F
Alcove Applications*
C
D
C
E
V
V
Combustible &
Noncombustible
V
V
V
E
 = Min. 6” (152 mm) for 
non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls
O
 = 8’ (2.4 m) Min.
O
P
584-15
 
No. 
  of Caps 
 
D
Min.
 
  C
Max.
 
3’ (914 mm)   x D
Actual
 
 
6’ (1.8 m) 
1 x D
Actual
 
9’ (.7 m) 
/3 x D
Actual
 
1’ (3.7 m) 
1/ x D
Actual
D
Min.
 = # of Termination caps x 3
C
Max.
 = ( / # termination caps) x D
Actual
*noTe: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or 
non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. . All mechanical air intakes within 10’ (1 m) of a 
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must 
be a minimum of 1’ (305 mm) below the termination cap.
GeneRal InFoRMaTIon aSSeMBlInG VenT pIpeS
uSa Installations
The venting system must conform to local codes and/or 
the current National Fuel Code ANSI Z3.1/NFPA 54.
Only  venting  components  manufactured  by  MHSC  may 
be used in Direct Vent systems.
Canadian Installations
The venting system must be installed in accordance with 
the current CSA-B149.1 installation code.
Flex Vent pipes
Before joining the flex vent pipe to the unit, apply a bead 
of  high  temperature  sealant*  (provided)  to  the  4”  pipe 
exiting the fireplace. Secure flex vent pipe in place with 
a hose clamp (provided).
*Be sure the flex pipe overlaps at least 1” (5 mm) onto 
the collars of the fireplace and termination. If the termi-
nation has an internal bead, be sure to overlap and se-
cure 1” (5 mm) past the bead.
* Be sure the vent is actually crushed before proceeding. 
Apply a tug to be sure the vent will not slip off the collars.
Repeat process with 7” flex vent pipe. The same proce-
dure must be performed on the vent side.
FP2290
flex vent
Apply High Temperature 
Sealant
Hose Clamp
FP90
Figure 10 - 
Apply high temperature sealant to 4” and 7” pipes.
Figure 9 - 
Termination Clearances