Monessen Hearth HBDV300N/PV7 User Manual

Page of 64
HBDV7 Series Direct Vent Gas Fireplace
54D8000
7
W
ARNING
Do  not  fill  spaces  around  firebox  with 
insulation or other materials. this could 
cause a fire.
FIReBox FRAMING 
Firebox framing can be built before or after the appliance 
is set in place. Refer to Figure 2 for fireplace and framing 
dimensions. Construct firebox framing following Figure 2 
for  your  specific  installation  requirements.  The  framing 
headers may rest on the top of the firebox standoffs. Do 
not bring headers below top of standoffs. 
The firebox may be installed directly on a combustible floor 
or  raised  on  a  platform  of  an  appropriate  height.  When 
the firebox is installed directly on carpeting, tile, or other 
combustible material, other than wood flooring, the firebox 
shall be installed on a metal or wood panel extending the 
full width and depth of the enclosure.
PRe-INStAllAtIoN INFoRMAtIoN
FIRePlACe loCAtIoN
Plan for the installation of your appliance. This 
includes 
determining where the unit is to be installed, the vent con-
figuration  to  be  used,  framing  and  finishing  details,  and 
whether any optional accessories (i.e. blower, wall switch, 
or remote control) are desired. Consult your local building 
code agency to ensure compliance with local codes, includ-
ing permits and inspections.
The following factors should be taken into consideration:
 
Clearance to side-wall, ceiling, woodwork, and windows. 
Minimum clearances to combustibles must be main-
tained.
  This fireplace may be installed along a wall, across a 
corner, or use an exterior chase. Refer to Figure 3 for 
suggested locations.
  Location should be out of high traffic areas and away 
from  furniture  and  draperies  due  to  heat  from  appli-
ance.
  Never obstruct the front opening of the fireplace.
  Do  not  install  in  the  vicinity  where  gasoline  or  other 
flammable liquids may be stored.
  Vent pipe routing. Refer to Venting section found in this 
manual for allowable venting configurations.
  These units can be installed in a bedroom. See National 
Fuel  Gas  Code ANSI  Z33.1/NFPA  54  —  (current 
edition), the Uniform Mechanical Code — (current edi-
tion), and Local Building Codes for specific installation 
requirements.
Y
E
A
B
C
D
F
Y
B
X
LU584-1
Locating unit
2/4/99   djt
  A  Flat on Wall
  B  Cross Corner
  C  Island**
  D  Room Divider*
  E  Flat on Wall Corner*
  F  Chase Installation
  Y  4” Minimum
**  Island (C) and room divider (D) installation is possible as long 
as the horizontal portion of vent system (X) does not exceed 
0'. Refer to Termination Location on Pages 12 and 13.  
When  you  install  your  fireplace  in  (D)  room  divider  or  (E) 
flat on wall corner positions (Y), a minimum of 6" clearance 
must  be  maintained  from  perpendicular  wall  and  front  of 
fireplace. 
Figure 3 - 
Fireplace Locations
N
ote
ColD ClIMAte INSulAtIoN
If  you  live  in  a  cold  climate,  seal  all  cracks  around  your  appliance,  and 
wherever cold air could enter the room, with noncombustible material. It 
is especially important to insulate the outside chase cavity between the 
studs and under the floor on which the appliance rests, if the floor is above 
ground level.