Monessen Hearth HBDV400N/PV7 User Manual

Page of 64
HBDV7 Series Direct Vent Gas Fireplace
54D8000
17
VeNt INStAllAtIoN
FP2294
Side View Vent Termination
1/25/00   djt
Finish Wall
Vent 
Termination
FP94
Figure 19 - 
Side View of Final Unit Location
ReAR WAll VeNt INStAllAtIoNS - 
Flex VeNt PIPe
Follow Steps 1 and  on Page 16.
Step 3
Install the 4” (10 mm) flex vent pipe to the appliance col-
lars  described  in  “General  Information Assembling  Vent 
Pipes”, Page 13.  If the installation requires a 45° angle, 
grasp the vent pipe close to the appliance collar and bend 
to 45°. DO NOT exceed 45°. Figure 20
Install the 7” vent pipe in the same manner as Step .
Note: There must be a 1/” (13 mm) rise in a 1”      (305 
mm) length of flex vent. 
Step 4
Assemble the flex vent to the collars on the termination as 
you did on the appliance.
FP1473
corner flex install
4/04  djt
Termination
Flex Section
Appliance Collars
FP1473
Figure 20 - 
Grasp the vent pipe close to the collar and 
bend to 45° angle. do not exceed 45°.
FP1472
rise in length
4/04  djt
Rise
FP147
Figure 21 - 
There must be a 1/2" rise per foot length
toP VeNt SIDeWAll APPlICAtIoN
Note: For all top vent installations where a 90° elbow is 
the first pipe piece towards a sidewall termination (up and 
out), an open-center ringed flue restrictor, part #69D3006 
must  be  installed  onto  the  top  edge  of  the  firebox  flue 
adapter.  To  create  this  open-center  restrictor,  twist  and 
break off the center rib of the supplied flue restrictor. The 
installed part should appear similar to that show n in Fig-
ure 22.
 
Since it is very important 
that  the  venting  system 
maintain  its  balance  be-
tween the combustion air 
intake  and  the  flue  gas 
exhaust, 
certain 
limitations  as  to 
vent configurations 
apply  and  must  be 
strictly adhered to.
The Vent Graph, showing the relationship between verti-
cal and horizontal side wall venting, will help to determine 
the various dimensions allowable.
Minimum clearance between vent pipes and combus-
tible materials is 3" (76 mm) on top, and 1" (25 mm) on 
the bottom and sides unless otherwise noted.
When  vent  termination  exits  through  foundations  less 
than  0”  (508  mm)  below  siding  outcrop,  the  vent  pipe 
must flush up with the siding.
It is best to locate the fireplace in such a way that mini-
mizes the number of offsets and horizontal vent length. 
The horizontal vent run refers to the total length of vent 
pipe from the flue collar of the fireplace (or the top of the 
Transition Elbow) to the face of the outer wall.
Horizontal plane means no vertical rise exists on this por-
tion of the vent assembly.
FP2303
CDV7 rear restrictor
3/09
Figure 22 - 
Top Vent Vertical Sidewall 
Restrictor
FP303