Monessen Hearth KHLDV400 User Manual

Page of 64
73D0024
51
KHLDV Series Gas Fireplace
trouBLeSHootInG 
StanDInG pILot IGnItIon
SyMptoM 
poSSIBLe cauSe 
actIon
1.  Spark ignitor will 
not light pilot after 
repeated triggering of 
piezo.
2.  Pilot will not stay lit 
after carefully follow-
ing lighting instruc-
tions.
3.  Pilot burning, valve 
knob turned to “ON,” 
switch is turned to 
“ON” or “RS,” but 
burner will not ignite. 
A.  Wire disconnected.
B.  Defective ignitor.
C.  No gas or low gas pres-
sure.
D.  No Propane/LPG in tank
A.  Defective thermocouple
B.  Defective valve
A.  Defective switch, wall 
switch, remote control or 
wire
B.  Pilot flame too small
C.  Defective or malfunction-
ing thermopile
D.  Defective valve
A.  Open door and check to make sure wire is connected to 
ignitor.
B.   Check for spark at electrode and pilot. If no spark and 
electrode  wire  is  properly  connected,  replace  pilot 
assembly. 
C.  Check remote/manual shut off valve from fireplace. Low 
pressure can be caused by bent lines, restricted lines, 
low pressure line pressure. Consult with plumber or gas 
supplier. 
D.  Check Propane/LPG tank. Refill tank.
A.  Check  that  thermocouple  flame  impinges  on  thermo-
couple.  Clean  and/or  adjust  pilot  for  maximum  flame 
impingement.  Ensure that the thermocouple connection 
at the gas valve is fully inserted and tight. 
 
Disconnect the thermocouple from the valve, place one 
millivolt lead wire on the tip of the thermocouple and the 
other meter lead wire on the thermocouple copper lead. 
Start the pilot and hold the valve knob in. If the millivolt 
reading is less than 15 mV, replace pilot assembly. 
B.   If thermocouple is producing more than 15 mV, replace 
faulty valve.
A.  Check  switch  and  wire  for  proper  connection.  Place 
jumper wires across terminals of switch. If burner comes 
on, replace defective switch.If the switch is OK, repeat 
the same procedure on remote control If burner comes 
on, replace remote control. 
 
Place jumper wire across wire at gas valves (terminals 
marked TH and TP/TH). If burner comes on, wires are 
faulty or connections are bad. Replace wire.
B.   If pilot flame is not close enough to the thermopile, adjust 
pilot flame.
C.   Check  thermopile  wire  connections  to  make  sure  all 
are  tight  and  that  the  thermopile  is  fully  inserted  into 
pilot assembly.  Check thermopile with a millivolt meter. 
Connect leads to TP and TP/TH terminals on the control 
valve. If meter reading is below 325 mV, replace pilot 
assembly.
D.   Turn valve knob to “On” and switch to “ON.” Take a read-
ing at the thermopile leads (TP & TP/TH) on the valve. 
If the meter reads greater than 175 mV and the burner 
does not light, replace defective valve.