VENT INSTALLATION 
VENT REQUIREMENTS
•  Make  sure  the  exhaust  pipe  on  heater  connects 
to  exhaust  portion  of  cap.  Attach  flex  liners.  See 
Figure 6.
•  Do  not  crimp  or  rupture  liner  when  bending  it  into 
chimney offsets.
W
ARNING
Figure 6 - Venting Unit 
Exhaust
Inlet
Maximum Height 
40' (12.9 M)
Minimum Height
10' (3 M) 
Maximum 
1' (305mm) 
Offset at 
Base of 
Insert 
•  Make sure you have the following before installing 
490 unit: 
  •   4" and 3" UL 1777 Listed gas liner for air 
inlet and exhaust 
  •   Vertical termination kit (AI42TK43A)
•  Make sure you have the following before installing 
380 unit: 
  •   3" and 3" UL 1777 Listed gas liner for air inlet and 
exhaust 
  •   Vertical termination kit (AI31TK33A)
•  The exhaust vent must reline the entire length of chimney and terminate above chimney top.
•  Vent must meet all vent manufacturerʼs requirements when installed.