ILDV20/ILDV30 Fireplace Insert
17
iNSeRt iNStALLAtiON
checK GAS tyPe
Use proper gas type for the insert you are installing. If you have conflicting gas type, do not 
install insert. See dealer where you purchased the insert for proper insert according to your 
gas type.
iNStALL GAS PiPiNG tO iNSeRt LOcAtiON
W
ARN
iNG
A  qualified  installer  or  service  person 
must  connect  appliance  to  gas  supply. 
Follow all local codes.
c
A
uti
ON
For propane/LP units, never connect insert directly to the propane/
LP supply. this burner system requires an external regulator (not 
supplied). install the external regulator between the burner system 
and propane/LP supply.
iNStALLAtiON iteMS NeeDeD
Make sure you have the items listed below before installing appliance.
  External regulator (supplied by installer) 
  Piping (check local codes) 
 Test gauge connection*
  Sealant (resistant to propane/LP gas) 
  Sediment trap (optional but recommended) 
  Tee joint 
  Pipe wrench 
  approved flexible gas line with gas connector (if allowed by local codes — not provided)
*  A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test 
gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will 
reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of wa-
ter. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external 
regulator with the vent pointing down as shown in Figure 12. Pointing the vent down protects it from freezing 
rain or sleet.
 
&0
EXTERNAL
External 
Regual-
tor
Vent 
Pointing 
Down
100 gal. (min. 
Propane/LP 
Supply Tank
FP1930
Figure 12 - External Regulator with Vent 
Pointing Down (Propane/LP Only)
c
A
uti
ON
use only new black iron or steel pipe. inter-
nally tinned copper or copper tubing can be 
used  per  National  Fuel  Gas  code,  Section 
2.6.3, providing gas meets hydrogen sulfide 
limits,  and  where  permitted  by  local  codes. 
Gas piping system must be sized to provide 
minimum inlet pressure (listed on data plate) 
at  the  maximum  flow  rate  (Btu/hr).  undue 
pressure  loss  will  occur  if  the  pipe  is  too 
small.