Monessen Hearth KHLDV SERIES User Manual

Page of 52
73D0024 
17
24" Min.
•   The maximum number of 90° elbows per side wall installation is three (3). See Figure 11. 
•   A minimum of 24" is required before a 90° elbow. If a 90° elbow is fitted directly after 24" vertical section mounted to 
the top of the fireplace, the maximum horizontal vent run before the termination or a vertical rise is 36” (914 mm). See 
Figure 12.
VENT INSTALLATION 
VERTICAL/HORIZONTAL TERMINATION 
CONFIGURATIONS
Since it is very important that the venting system maintain its balance between the combustion air intake and the flue 
gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical and horizontal side wall venting, will help to determine the vari-
ous dimensions allowable. See Figure 10. 
NOTE: Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at the top of the 
fl ue and 1" clearance at the sides and bottom until the fl ue penetrates the outside wall. A minimum 1" clearance all 
around the fl ue is acceptable at this point of penetration.
Vertical sections of this vent system require a minimum of 1" clearance to combustibles on all sides of the pipe.
 
When vent exits through foundations less than 20" below outcrop, the termination must be flush up with outcropped wall 
above.
It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length.
The horizontal vent run refers to the total length of vent pipe from the flue collar of the fireplace (or the top of the Transition 
Elbow) to the face of the finished outside wall. 
Figure 11 - Maximum Three (3) 90° Elbows 
Per Installation
Figure 12 - Maximum Horizontal 
Run with No Rise
3 x 90°
Elbows
36"
Max.
36"
Max.
24" Min.