Monessen Hearth SBV500 User Manual

Page of 42
62D4036 
17
COMBUSTION AIR ASSEMBLY 
MODEL OAC-4 COMBUSTION AIR ASSEMBLY
1.  Remove the cover plate from the 4" outlet opening location on the left outside 
of the fireplace. 
2.  Place starting collar (4") into hole on left side of fireplace. Fireplace shortest 
side of air starting collar through fireplace outer wrap. Fasten starting collar 
in place with four (4) sheet metal screws provided. See Figure 13.
Note:  The air starting collar extends through the fireplace outer wrap. When the air starting collar is 
securely attached, it will form a seal against the fireplace wall.
3.  Cut a 6" diameter opening for model OAC-4 in the outside 
wall covering where the outside vent is to be located. See 
Figure 15.
4.  Select and cut a piece of duct long enough to attach to the 
fireplace and stick out at least 3" beyond the face of the 
wall to which the OAC-4 inlet air vent will be attached. 
Cut duct with a standard pocket knife. See Figure 14.
DO NOT remove the 
cover if the outside air 
will not be connected.
W
ARNING
Figure 13 - Attaching Outside Air 
Starting Collar to Left Side of Fireplace 
Figure 14 - Attaching Outside Duct 
to Starting Collar
OAC-4 
Starting 
Collar 
Sheet 
Metal  
Screws 
Left Side of 
Fireplace 
Shorter End of Air 
Starting Collar 
Air Starting 
Collar 
Duct 
Screws 
Left Side of 
Fireplace 
Figure 15 - Combustion Air Assembly for 
Model No. OAC-4
Nail 
Holes 
6" Diameter 
Hole 
Duct 
Extending
3"min. 
AK-4 Inlet 
Air Vent 
Screw
Screws
5.  If using insulating duct, push the insulation back from 
one end of the duct approximately 2". See Figure 15.
6.  Slip the exposed end of the duct over the starting collar 
on the fireplace.
7.  Using the sheet metal screws provided, secure the duct 
end to the collar attached to the fireplace.
8.  Nail or screw the combustion air assembly to the sur-
face of the wall.
Do not use a combustible duct. Always 
use  UL  Listed  Class  0  or  1  duct 
material.  If  necessary  to  splice  duct, 
use Model 403 duct connector to splice 
duct sections. 