WDV Series Gas Fireplace
sIGnature cOMManD - checK Gas pressure and electrIcal InstallatIOn
1.  Check gas type. The gas supply must be the same as 
stated on the appliance’s rating decal. If the gas supply 
is different from the fireplace, stOp! Do not install the 
appliance. Contact your dealer immediately.
2.  To ease installation, a 24" (610 mm) flex line with manual 
shut-off valve has been provided with on this appliance. 
Install and attach 1/2" gas line onto shut-off valve. 
3.  After  completing  gas  line  connection,  purge  air  from 
gas line and test all gas joints from the gas meter to the 
fireplace for leaks. Use a solution of 50/50 water and 
soap solution or a gas sniffer. 
4. To check gas pressures at valve, turn captured screw 
counter clockwise 2 or 3 turns and then place tubing to 
pressure gauge over test point. Turn unit to high. Fig-
ure 31 
After taking pressure reading, be sure and turn 
captured screw clockwise firmly to reseal. Do not over 
torque. Check test points for gas leaks.
FP1909a
signature command valve
alternate view
8/08
Pressure Inlet
Pressure Outlet
Pilot Adjust-
ment Screw
FP1909a
Figure 31 - 
Signature Command Valve
electrIcal WIrInG
Verify proper operation after servicing. 
This fireplace will work without any electrical supply. Electricity is only needed to operate blower.
nOte: If installed in mobile home, fireplace must be bolted securely to floor. 
W
arn
In
G
Do not use open flame to check for gas 
leaks.
W
arn
In
G
electrical  connections  should  only 
be  performed  by  a  qualified,  licensed 
electrician. Main power must be off when 
connecting to main electrical power supply 
or performing service. all wiring shall be 
in compliance with all local, city, and state 
codes. the appliance, when installed, must 
be  electrically  grounded  in  accordance 
with  local  codes,  or  in  the  absence  of 
local  codes,  with  the  National  Electrical 
Code ANSI/  NFPA  70  (latest  edition)  
and 
Canadian Electrical Code, CSA C22.1.
caut
IO
n
label all wires before disconnecting when 
servicing controls. Wiring errors can cause 
improper and dangerous operation.