Monessen Hearth BDV600 User Manual

Page of 52
54D0700 
13
1"
3"
1"
1"
VENT INSTALLATION 
This  fi replace must be vented to the outside. The venting system must NEVER be 
attached to a chimney serving a separate solid fuel burning appliance. Each gas 
appliance must use a separate vent system. Do not use common vent systems. 
W
ARNING
Horizontal sections of this vent system require 
a minimum of 3" clearances to combustibles at 
the top of the fl ue and 1" clearance at the sides 
and bottom until the fl ue penetrates the outside 
wall. 
A minimum 1" clearance all around the fl ue 
is acceptable at this point of penetration.
Vertical sections of this vent system require a 
minimum of 1" clearance to combustibles on all 
sides of the pipe.  
Figure 7 - Combustible Clearances for Vent Pipe 
A Minimum of 3" Clearance 
to the Top Is Required Along 
Horizontal Length until Flue 
Pipe Penetrates Outside Wall. 
W
ARNING
A Minimum 1" 
Clearance to 
Combustibles 
Permitted All 
Around Flue 
at Outside 
Wall