Hearth & Home Technologies Cinch Pipe & Termination Cap System User Manual

Page of 12
Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05
5
3 in. (76 mm)
top clearance
1 in. (25 mm)
clearance
bottom & sides
Heat
Shield
Wall
Shield
Heat
Shield
WALL
Note: Heat shields
MUST overlap by a
minimum of
1-1/2 in. (38 mm).
Figure 2.2 
Horizontal Venting Clearances to Combustible Materi-
als - Rear Vent
A.  Clearances for the Vent Sections
•  
Top Vented Direct Vent Appliances
For all top vented, direct vent appliances, clearances to 
combustible materials from the venting system need to 
be maintained as shown in Figure 2.1.
•  Rear Vented Direct Vent Appliances
  See Figure 2.2.
Figure 2.1 
Horizontal Venting Clearances to Combustible Materi-
als - Top Vent
Note:  
For termination cap installations only, go directly to Sec-
tion E.
Note:  
Refer to the appliance installation instructions for al-
lowed vent lengths and confi gurations.
Installing Vent Pipe 
B.  Penetrating a Wall
Wherever a  combustible wall is penetrated, the hole must 
be framed with an interior wall shield (DVP-WS) as shown in 
Figures 2.3-2.4. This shield maintains minimum clearances 
and restricts cold air infi ltration. If the wall being penetrated is 
of noncombustible materials (material which will not ignite or 
burn, or has a UL fi re rating of zero), a 9 in. diameter hole is 
acceptable. Whenever a wall is penetrated the wall shield is only 
required on one side and no heat shield is necessary. If your 
local inspector requires the wall shield on both sides, then both 
wall shields must have a heat shield attached to them.
Figure 2.4 
 Interior Wall Shield
Figure 2.3 
 Exterior Wall Hole
Note:  
 Heat shields MUST overlap by 1-1/2 in. min. for rear 
vented appliances.
Fire Risk
Explosion Risk
Maintain vent clearance to combustibles as 
specifi ed.
•  Do not pack air space with insulation or 
other materials.
Failure to keep insulation or other materials 
away from vent pipe may cause fi re.
WARNING