Hearth & Home Technologies PMH User Manual

Page of 32
Page 7
Yosemite Wood Stove
7004-187F   September 1, 2008
R
FLOOR PROTECTION
The floor must be non-combustible material, extending beneath heater and to the front/sides/rear as indicated.  The floor must be 
non-combustible or otherwise adequately protected from radiant heat given off by the unit and from sparks and falling embers.  A 
layer of thin brick or ceramic tile over a combustible floor is not sufficient.  
In USA installations, it is necessary to install a non-combustible floor protector at least 16 inches in front and 8 inches to both 
sides of the fuel loading doors.  See *exception below.
In Canada, similar floor protection must be provided 18 inches (450mm) in front and 8 inches (200mm) from the sides and rear of 
the stove.  See *exception below.
*EXCEPTION:  Non-combustible floor protections must extend beneath the flue pipe when installed with horizontal venting and 
extend 2 inches (51mm) beyond each side.
Minimum 16"
 
(406mm) from 
fuel loading
 
door
8"
(200mm)
USA
44-1/2"
(1130mm)
 
Minimum
36-3/4"
(932mm)
Minimum
 Fuel loading doors
Front
Side
8"
(200mm)
Minimum 450mm 
(18")
 from each 
fuel loading door
CANADA
1187mm
(46-3/4")
Minimum
 Fuel loading doors
Front
Side
200mm 
(8")
1264mm 
(49-3/4")
 
Minimum
200mm
 
(8")
CANADA
200mm (
8")
200mm
(
8")
450mm 
(18")
1187mm 
(46-3/4")
Minimum
1010mm 
(39-3/4")
 
Minimum
200mm
(
8")
SIDE FUEL DOOR LOCKED SHUT
BOTH FUEL DOORS ACCESSIBLE
DRAWINGS ARE FOR ILLUSTRATION PURPOSES ONLY AND ARE NOT TO SCALE.
16"
 
(406mm)
 
from fuel 
loading door 
8" 
(200mm) 
USA 
Front Fuel 
loading door 
33"
(838mm)
 Minimum 
36-3/4
(933mm)
 
Minimum 
10-1/2"
(267mm)
Minimum Hearth Requirements ONLY
See page 6 for stove clearances