Heat & Glo · Tiara I B & Tiara II B · 7010-149M
D. 
How to Use the Vent Graph
E. 
Venting Guidelines
1
.  Measure the distance from the top of appliance to the 
center of the 90° elbow. On the graph below, draw a 
horizontal line from that measurement on the vertical 
axis across until it intersects with the slanted  line.
2.  From the point of this intersection, draw a vertical line to 
the bottom of the graph.
3.  The point at which this line meets the bottom line of the 
graph is the maximum length of the horizontal run. 
Example 1: If the vertical dimension from the center line of 
the fl ue vent to the center of the 90° elbow is 7 ft. (2m), the 
horizontal run to the outer wall fl ange must not exceed 16 
ft. (5m).
.
Example 2:  If the vertical dimension from the center line of 
the fl ue vent is 21 ft. (6m), the horizontal run to the outer wall 
fl ange must not exceed 12 ft. 10 in. (4m).
4.  Each 90° elbow is equivalent to 3 ft. (914mm) of vent 
pipe and each 45° elbow is equivalent to 1 ft. (305mm) 
of vent pipe, and must be subtracted from the vent pipe 
run. A single horizontal to vertical 90° elbow is already 
calculated into the allowable 
20 ft. (6m) run. Each additional 
90° elbow reduces the 
maximum horizontal distance 
by 3 ft. (914mm).
Example:  The use of 3 elbows 
would reduce the allowable 
horizontal run to 9 ft. (3 -1 =  
2 elbows x 3 ft. = 6 ft.; 20 ft. 
max. - 6 ft. = 14 ft. max.).
•  The maximum horizontal vent run is 20 ft. (6m) when the 
vertical vent rise is 10 ft. (3m).
•  The minimum horizontal vent run is 6 in. (152mm).
•  Horizontal sections require a 1/4 in. (6mm) rise for every 
12 in. (305 mm) of horizontal travel.
•  Exterior Vent Diameter = 6-5/8 in. (168mm); Inner Vent 
Diameter = 4 in. (102mm).
•  Horizontal sections require noncombustible support 
every 3 ft. (914mm), e.g. wall straps.
•  For any vertical termination a minimum of 6 ft. (2m) 
 
vertical must be used.
Figure 5.2
SLK-01TRD 
Example 1 
Example 2 
2'           4'          6 '          8'          10'         12'        14'   15'  16'  17'  18'  19'  20' 
2' 
4' 
6' 
8' 
10' 
12 
14' 
16' 
18' 
20' 
22' 
24' 
26' 
28' 
30' 
32' 
34' 
35' 
36' 
37' 
38' 
39' 
40' 
Part #SLK-991DA 
3 ft. (914mm) Maximum Horizontal run with no vertical pipe 
and with 1/4 in. (6mm) rise per foot. Must use Snorkel cap. 
Damper position 
more CLOSED in 
this area 
6 ft. (2m) Minimum V ertical T erminatio 
For rear vent or top of 
stove for top vent. 
6 in. (152mm) Minimum starter pipe 
40 ft. (12m) 
Maximum V ertica 
VERTICA 
L  DIS T ANCE 
FROM APPLIANCE 
T O 90 
° 
ELBOW 
Damper position 
more OPEN in 
this area 
NO Damper in 
this area 
EXCEPTIONS FOR HORIZONTAL INSTALLATIONS:
*When installing the Tiara I-B or Tiara II-B in a rear vent 
configuration with no vertical rise, a Snorkel Kit must be 
used. Refer to venting components.
*The maximum horizontal vent run is 3 ft. (914mm).
*The maximum horizontal vent run with a 45° elbow is 2 ft.  
(609mm).
*The minimum horizontal vent run is 6 in. (152mm).
NOTE:  
IF YOUR INSTALLATION FALLS WITHIN A SHADED AREA ON 
THE GRAPH, THE DAMPER MUST BE USED.* SEE INFORMATION ON 
DAMPER ADJUSTMENT ON PAGE 31.
*In the Commonwealth of Massachusetts, the word damper shall be replaced 
with the words flue restrictor.