Hearth & Home Technologies TIARA I-B User Manual

Page of 60
Page  14
August 1, 2008
Heat & Glo · Tiara I B & Tiara II B · 7010-149M
NOTE:
(1) Installation requires a minimum of 6 in. (152mm) 
horizontal run of vent with a 1/4 in. (6mm) rise run towards 
the termination. Each 1 ft. (305mm) of horizontal venting 
must include a 1/4 in. (6mm) rise.  Never allow the vent 
to run downward. This could cause high temperatures 
and may present the possibility of a fire.
(2)  The location of the horizontal vent termination on an 
exterior wall must meet all local and national building 
codes, and must not be easily blocked or obstructed, 
see 
Figure 4.4 on page 10. 
(3)  For installations requiring a vertical rise on the exterior 
of the building, a snorkel kit is available with a 14 in. 
(356mm) and a 36 in. (914mm) tall snorkel termination 
cap.  Follow the same installation procedures as used 
for standard horizontal terminations. If the  snorkel 
termination must be installed below grade (i.e. basement 
application), proper drainage must be provided to 
prevent water from entering the snorkel termination.  Do 
not backfill around snorkel termination.
HOT 
HOT 
 
WOOD
SCREW
WALL THIMBLE
NOTES:
(1)  The four wood screws provided should be replaced with 
appropriate fasteners for stucco, brick, concrete, or 
other types of sidings.
(2)   A termination cap with a built-in vinyl standoff is  highly 
recommended on a building with vinyl siding. The pilot 
hole will be 2 in. (51mm) closer to the bottom of the 
square than the top. Using a framing square, draw a 14 
in. x 14 in. (356mm x 356mm) square around the pilot 
hole. See
 Figure 5.7.
8 in. 
(203mm)
7 in. 
(178mm)
7 in. 
(178mm)
6 in. 
(152mm)
Figure 5.6
Figure 5.7
Figure 5.5
CENTER 
LINE
CENTER OF 
HOLE
WALL 
THIMBLE
CENTER 
LINE
Step 3. 
For installations using a round support box/wall thimble 
(check pipe manufacturer's instructions), mark the wall for a 
10 in. x 10 in.  (254mm x 254mm) square hole.  The center 
of the square hole should line up with the center line of the 
horizontal pipe, as shown in 
Figure 5.5.  Cut and frame the 
hole in the exterior wall where the vent will be terminated.  If 
the wall being penetrated is constructed of noncombustible 
material, i.e. masonry block or concrete, a 7 in. (178mm) 
diameter hole is acceptable.  
Step 4. 
Position the horizontal termination cap in the center of the 10 
in. x 10 in. (254mm x 254mm) square hole and run a bead 
of non-hardening mastic around its outside edges, so as to 
make a seal between it and the wall, attach termination cap 
to the exterior wall with the four wood screws provided. The 
arrow on the vent cap should be pointing up (
Figure 5.6). 
  
(
NOTE:  Some termination caps may cause the vent 
pipe to be off center on flashing.).  Ensure that proper 
clearances to combustible materials are maintained. 
 If 
you are not using an approved termination cap with a built-
in standoff on a building with vinyl siding, a vinyl siding 
standoff should be installed between the termination 
cap and the exterior wall (
Figure 5.8, on the next page). 
Follow manufacturer’s instructions for attaching the 
vinyl siding standoff to the horizontal termination cap. 
The vinyl siding standoff prevents excessive heat from 
possibly melting the vinyl siding material. The vent 
terminal cap shall not be recessed into a wall or siding.  
Remove siding from the area where the standoff will be 
located.