Hearth & Home Technologies HUDBAY-FS User Manual

Page of 49
10/08
Page  11
Quadra-Fire  •  Hudson Bay  •  7003-121 Rev. i
D. 
How to Use the Vent Graph
E. 
Venting Guidelines
Figure 5.2
NOTE: I F YOUR INSTALLATION FALLS WITHIN A SHADED 
AREA ON THE GRAPH, THE DAMPER MUST BE USED.
  
(In the Commonwealth of Massachusetts, the word damper 
shall be replaced with the words flue restrictor.)
1.  Measure the distance from the top of appliance to the 
center of the 90° elbow. On the graph below, draw a 
horizontal line from that measurement on the vertical 
axis across until it intersects with the slanted line.
2.  From the point of this intersection, draw a vertical line to 
the bottom of the graph.
3.  The point at which this line meets the bottom line of the 
graph is the maximum length of the horizontal run. 
4.  Each 90° elbow is equivalent to 3 ft. (914mm) of vent 
pipe and each 45° elbow is equivalent to 1 ft. (305mm) 
of vent pipe, and must be subtracted from vent pipe 
run. A single vertical to horizontal 90° elbow is already 
calculated into the allowable 15 ft. (5m) run. Each 
additional 90° elbow reduces the maximum horizontal 
distance by 3 ft. (914mm).
VERTICAL DISTANCE
FROM APPLIANCE TO
TO THE 90° ELBOW
TOTAL HORIZONTAL RUN TO OUTSIDE OF EXTERIOR WALL (INCLUDING ELBOWS)
EX. 2
EX. 1
     11"   2'        4'         6'        8'       10'      12'      14'  15'
30'
28'
26'
24'
22'
20'
18'
16'
14'
12'
10'
 8'
 6'
 4'
 2'
 0'
(MAX)
(MIN)
40'
38'
36'
34'
32'
NOTES
The maximum horizontal vent run is 15 ft. (5m) with a minimum 
vertical vent rise of 10 ft. (3m).
The minimum horizontal vent run is  11 in. (279mm).
Minimum wall thickness is 4 in. (102mm).  Maximum wall 
thickness is 20 in. (508mm).
Horizontal sections require a 1/4 in. (6mm) rise for every 12 
in. (305mm) of horizontal travel.
Exterior Vent Diameter = 6 5/8 in. (168mm); Inner Vent Diam-
eter = 4 in. (101mm) 
Horizontal sections require noncombustible support every 3 
ft. (914mm), e.g. wall straps.
Maximum 90° elbows for horizontal termination is 3.
Maximum 90° elbows for vertical termination is 4.
Example 1:
If the vertical dimension from the top of the 
appliance is to the center of the 90° elbow is 
7 ft. (2m), the horizontal run to the outer wall 
flange must not exceed 12 ft. (4m).
Example 2:
If the vertical dimension from the top of the 
appliance is 21 ft. (6m), the horizontal run 
to the outer wall flange must not exceed 9 
ft. (3m).
Example:
The use of 3 elbows would reduct the 
alowable horizontal run to 9 ft. (3 - 1 = 2 
elbows x 3 ft. = 6 ft.; 15 ft. max. - 6 ft. = 9 
ft. max.)