SECTION A:  FRAMING  
EBU Dimensions 
 
 
 
 
 
Rough-in framing dimensions  
      EBU dimensions             
    Rough-in corner framing dimensions 
 
This fireplace is a zero clearance design. Combustibles may be installed to the edge of the unit. A drywall lip at the top 
of the unit and four nailing flanges on the sides of the unit are provided on each unit to facilitate installation.  Insulation 
and vapor barrier can
 
be placed a minimum of 2 inches from the unit.   
 
SECTION B: RECOMMENDED POWER SUPPLY WIRE SPECIFICATIONS 
For 120 volt installations use two conductors, non-metallic sheath cable with ground wire for the incoming power supply 
on EBU fireplace inserts. Use the appropriate wire to meet local and national electrical codes for rated power 
consumption.   
 
For 208 / 240 volt installations use three conductors, non-metallic sheath cable with ground wire for the incoming power 
supply on EBU fireplaces. Use the appropriate wire to meet local and national electrical codes for rated power 
consumption. 
 
 
Two conductors, non-metallic sheath cable with ground wire is recommended for installation of a wall mounted 
thermostat on EBU fireplaces. Use appropriate wire to meet local and national electrical codes for rated power 
consumption. Thermostat switch wire gauge must match the recommended wire sizes shown below. 
 
 
 
 
     
 
RECOMMENDED WIRE AND FUSING REQUIREMENTS 
 
 
VOLTS 
WIRE GAUGE 
FUSE RATING 
120 VOLT 
12 GAUGE 
20 AMP 
208 VOLT 
14 GAUGE 
15 AMP 
240 VOLT 
12 GAUGE 
20 AMP 
MODEL A B C D E F 
36-EBU  35.5” 38.7” 54.0” 38.0” 38.0” 40.0” 
42-EBU  41.5” 44.7” 60.0” 42.0” 42.0” 46.0”