Hearth & Home Technologies 4100I-GD-B User Manual

Page of 28
Page 5
 
September 1, 2008
4100-I  ACT WOOD INSERT
250-7201E
R
Hearth Extension  
Insert 
SideW
all  
Maximum Mantel Depth - 10" (254mm)  
Fascia or Trim  
Mantel  
Thermal protection USA & Canada 
 
 
 
 
 
   USA
     
CANADA
A  Sidewall to Stove 
 
 15" (381mm)   15" (381mm)
B  Mantel to Stove   
 
 26" (660mm)    23" (584mm)
C   Top Trim to Stove 
 
 20" (508mm)   20" (508mm)
D  Side Trim to Stove 
 
   6" (152mm)     6" (152mm)
E  Hearth Extension from Glass 
 16" (406mm)   18" (457mm)
F  Hearth Extension from Side of Insert     8" (203mm)     8" (203mm)
Thermal protection must be 1/2 Inch (12.7mm) minimum 
thickness ('k" value = 0.84) or equivalent material*
*Zero Clearance Installations USA Only
Omni Report #061-S-40-2
In Canada a full length six inch (152mm) S65 flue liner 
required as per ULC S628.
CLEARANCES TO COMBUSTIBLES
United States and Canada
*
See Alternative Floor Protection Worksheet on page 7.
NOTE:  When installing into a masonry fireplace, the fire-
place must be built to UBC Chapter 7 standards.  Do not 
remove  brick  or  mortar  from  masonry  fireplace  to  accom-
modate insert.  The permanent metal warning plate provided 
must be attached to the back of the fireplace stating the fire-
place may have been altered to accommodate the insert and 
must be returned to original condition for use as a conven-
tional fireplace.