The minimum clearance to combustibles is 6” (150 mm) when using single wall venting and 1” (25 mm) 
when using “B-vent” venting.
We  strongly  recommend  installing  an  approved  chimney  liner  in  an  existing  brick  chimney.  This  will 
maximize the potential draft of the chimney and lessen the effects of slow chimney start-up. 
VENTING OF A FIREPLACE FITTED WITH THE DRAFTHOOD ADAPTOR:
Note:
  Please  refer  to  the  chimney  manufacturer’s  installation  instructions  prior  to  commencing  the 
installation.
Figure 46: Unit top venting styles.
4" (10cm) 
vent
6" (15cm) 
optional 
decorative 
cover
Check vent draft 
at the top row of 
opening.
Figure 48: Draft test place.
Figure 47: Unit rear 
venting style.
mm) must be maintained between the vent connector and any combustibles.
CAUTION:  A  minimum  vent  height  of  12’  (3.6  m)  from  the  floor  is  required  to  effectively  vent  this 
fireplace.
This  unit  may  be  vented  to  an  existing  masonry 
chimney, or where no masonry chimney is available, 
an approved “B-vent” chimney, or any other approved 
constructed chimney/vent system (see Figure 46 & 
47).
In  either  case,  the  fireplace  may  be  connected  to 
the chimney/vent using a 4” (10 cm) single wall vent 
connector.
When  an  existing  masonry  chimney  is  utilized  for 
the venting, we recommend the vent connector be 
connected to an approved 4” (10 cm) diameter flue 
liner running the full height of the chimney. In many 
jurisdictions this flue liner may be mandatory.
If 4” (10 cm) single wall vent is used, a minimum of 
6”  (15  cm)  must  be  maintained  between  the  vent 
connector and any combustibles.
If 4” (10 cm) “B-vent” is used a minimum of 1” (25 
30
Initial Installation
SPILLAGE TEST:
A  spillage  test  must  be  performed  prior 
to  leaving  the  installed  fireplace  with  the 
customer.  Perform  this  test  in  the  following 
manner:
1. Close all windows and doors in the room.
2. Start all exhaust fans in the house and the 
furnace blower.
3.  Light  the  fireplace  and  set  to  maximum 
flame adjustment.
4. After a minimum of 10 minutes operation, 
test the chimney draft with a smoke match 
at  the  top  row  of  the  pattern  to  confirm 
that there is adequate draft or ‘pull’ at the 
openings around the body of the Drafthood 
Adaptor, as shown in Figure 48.