Enviro DV36 User Manual

Page of 40
23
Wall framing
Horizontal wall
termination
Wall thimble
fire stop
Exhaust
flex pipe
Combustion air
outer pipe
Elbow
Initial Installation
QUALIFIED INSTALLERS ONLY
H
ORIZONTAL
 T
ERMINATION
:
NOTES:
1. Horizontal  pipes  must  not  be  level.  For  every  12  inches  (305  mm)  of  horizontal  travel 
(away from the stove), there should be at least 1⁄4 inch (6.4 mm) of vertical travel. Never 
allow the vent to run downward, as this could cause high temperatures or even present 
the possibility of a fire.
2. The  exterior  of  the  horizontal 
vent  termination  must  not  be 
blocked or obstructed.
3. If  the  vent  termination  is  not 
being  attached  to  wood,  the 
four  wood  screws  provided 
should  be  replaced  with 
material appropriate fasteners.
4. For  buildings  with  vinyl  siding, 
a  vinyl  standoff  should  be 
installed between the vent cap 
and  the  exterior  wall.  Attach 
the  vinyl  siding  standoff  to 
the  horizontal  termination. 
Note  that  the  termination 
bolts  onto  the  flat  portion  of 
the  standoff,  providing  an  air 
space  between  the  wall  and 
the  vent  termination.  The  air 
gap  prevents  excessive  heat 
from possibly melting the vinyl 
siding.
5. Horizontal  pipes  must  be 
supported  every  3  feet  (914 
mm). Plumber’s all round strap will suffice.
6. When running horizontal pipe, clearances to combustibles must be maintained 11⁄2 inches (38 mm) 
sides, 11⁄2 inches (38 mm) bottom, and 2 inches (51 mm) top.
Step 1.  Set the fireplace in the desired location. Check to determine if wall studs will be in the way when 
the venting system is attached. If this is the case, the location of the fireplace may have to be 
adjusted or the venting may have to be offset.
Step 2.  Direct vent pipe sections are designed with special twist-lock connections. Dry fit the desired 
combination of pipe and elbows to the appliance adaptor.
Step 3.  With the pipe in the correct position and attached to the fireplace, mark the wall for a 10 inches 
(25.4 cm) x 10 inches (25.4 cm) square hole (see Figure 29). The center of the hole should 
match the center line of the horizontal pipe. Cut and frame the hole in the exterior wall where 
the vent will be terminated. If the wall being penetrated is made of a non-combustible material 
(i.e. masonry or concrete) a 7 inches (17.8 cm) hole is acceptable.
Figure 33.  Horizontal Vent Termination