II  Restrictions ]
- 42 -
HWE08040
GB
P144 - P360 models
The figure shows a system with three outdoor units. (P264-P360 models)
Unit: m [ft]
Operation
Pipe sections
Allowable length of 
pipes
Length
Between outdoor units
A+B+C+D
10 [32] or less
Total pipe length
A+B+C+D+E+F+G+I+J
+K+M+a+b+c+d+e+f+g
+i
1000 [3280] or less
Total pipe length (L) from the outdoor unit to the 
farthest indoor unit
A(B)+C+E+J+K+M+i
165 [541] or less
(Equivalent length 190 
[623] or less)
Total pipe length from the first branch to the far-
thest indoor unit (
)
G+I+J+i
40 [131] or less
Height 
difference
Between indoor and outdoor units
H
50 [164] or less
(40  [131] or below if 
outdoor unit is below in-
door unit)
Between indoor units
h1
15 [49] or less
Between outdoor units
h2
0.1[0.3] or less
Indoor Indoor  Indoor Indoor 
Indoor Indoor  Indoor Indoor 
E
L
H
a
h1
h2
b
2
1
c
3
d
4
e
5
f
6
g
7
i
8
C
E
F
G
I
J
K
M
B
D
A
First branch 
(Note)
To downstream units 
Note : "Total sum of downstream unit model numbers" 
           in the table is the sum of the model numbers 
           of the units after point E in the figure. 
Note1  Install the pipe that connects the branch pipe and the outdoor units in  
the way that it has a downward inclination toward the branch pipe. 
Provide a trap on the pipe (gas pipe only) within 2 m from the
joint pipe if the total length of the pipe that connects the joint
pipe and the outdoor unit exceeds 2 m. 
Downward inclination 
To indoor unit 
To indoor unit 
To indoor unit 
Joint pipe
Joint pipe
Trap  
(gas pipe
only)
To indoor unit 
Upward inclination 
First liquid refrigerant distributor 
First gas refrigerant distributor 
Second gas refrigerant distributor 
Second liquid refrigerant distributor 
2m [6ft]
2m [6ft] Max.