Mitsubishi Electronics PEH-5MYA User Manual

Page of 115
- 88 -
PU(H)-7,8, 10 (Upper blow)
(1) At a single installation
The obstacle is on the outlet side. (Fig 1)
The obstacle is in three directions. (Fig 2,3)
The obstacle is in four directions. (Fig 4) 
The right and left side 
and the back and forth 
side must be opened.
However, the 
outlet side must 
be opened.
Fig 2
Service Panel
500 over
300 over
300
over
Fig 1
ceiling
1200
over
However, if the service 
panel is an interior side, 
the right or left side 
need 500 over.
If this side is service
panel, you need 500
over. If this side is inlet,
you need 300 over.
300 over
300 over
Fig 4
All "A" is 500 over.
However, outlet side 
must be opened.
And the obstacle in 
two directions must be 
lower than the unit.
A
A
AA
Fig 3
(2) Relation of unit when many set up unit. (Fig 5,6,7)
Fig 6
Fig 5
All "A" is 500 over.
500 over
500
over
300 over
300 over
500 over
300 over
A
A
A
A
300 over
Service-panel
If this side is
service panel,
you need 500 over.
If this side is inlet,
you need 300 over.
300 over
Fig 7 All "A" is 500 over in any case.
A
A
A
A
A
Service-panel