Mitsubishi P96 User Manual

Page of 334
VIII  Test Run Mode ] 
- 145 -
HWE09120
GB
Operation
Outdoor unit model
PUHY-P264TSJMU-A
PUHY-P120TJMU-A
PUHY-P144TJMU-A
Operating 
conditions
Ambient 
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor 
unit
No. of connected 
units
Unit
3
4
No. of units in opera-
tion
3
4
Model
-
36/36/36
36/36/36/36
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
35 [114-13/16 ]
45 [147-5/8]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
25 [55]
Outdoor 
unit
Electric current
A
67.4
Voltage
V
230
Compressor frequency
Hz
81
102
LEV open-
ing
Indoor unit
Pulse
332/332/332
332/332/332/332
SC (LEV1) 
0
0
LEV2
2100
2100
Pressure
High pressure (after O/S)/low 
pressure (before accumulator)
MPa
[psi]
2.72/0.63 [395/91]
2.72/0.63 [395/91]
Temp. of 
each sec-
tion
Outdoor 
unit
Discharge (TH4)
°C [°F]
70 [158]
89 [192]
Heat exchanger out-
let (TH3)
-1 [30]
-3 [27]
Accumulator inlet
-1 [30]
-3 [27]
Accumulator outlet
-1 [30]
-3 [27]
Compressor inlet
-1 [30]
-3 [27]
Compressor shell 
bottom
40 [104]
40 [104]
Indoor 
unit
LEV inlet
37 [98]
37 [98]
Heat exchanger  
inlet
75 [166]
75 [166]