Mitsubishi P336 User Manual
[
VIII Test Run Mode ]
- 148 -
HWE09120
GB
Operation
Outdoor unit model
PUHY-P336TSJMU-A
PUHY-
P96TJMU-A
PUHY-
P120TJMU-A
PUHY-
P120TJMU-A
Operating
conditions
conditions
Ambient
tempera-
ture
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
unit
No. of connected
units
units
Unit
6
No. of units in opera-
tion
tion
6
Model
-
54/54/54/54/54/54
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe
10 [32-3/4 ]
Total pipe length
65 [213-1/4]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
32 [70]
Outdoor
unit
unit
Electric current
A
79.7
Voltage
V
230
Compressor frequency
Hz
65
74
74
LEV open-
ing
ing
Indoor unit
Pulse
395/395/395/395/395/395
SC (LEV1)
171
171
171
LEV2
2100
2100
2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
pressure (before accumulator)
MPa
[psi]
2.89/0.88
2.89/0.88
2.89/0.88
[419/128]
[419/128]
[419/128]
Temp. of
each sec-
tion
each sec-
tion
Outdoor
unit
unit
Discharge (TH4)
°C [°F]
74 [165]
73 [163]
73 [163]
Heat exchanger out-
let (TH3)
let (TH3)
46 [115]
40 [104]
40 [104]
Accumulator inlet
10 [50]
10 [50]
10 [50]
Accumulator outlet
10 [50]
10 [50]
10 [50]
SCC outlet (TH6)
26 [79]
20 [68]
20 [68]
Compressor inlet
14 [57]
15 [59]
15 [59]
Compressor shell
bottom
bottom
38 [100]
42 [108]
42 [108]
Indoor
unit
unit
LEV inlet
21 [70]
21 [70]
21 [70]
Heat exchanger
outlet
outlet
10 [50]
10 [50]
10 [50]