Mitsubishi P336 User Manual

Page of 334
IX  Troubleshooting ]
- 270 -
HWE09120
GB
(2)  Troubleshooting transmission power circuit of outdoor unit
1)   PUHY-P72TJMU-A
Check the voltage between No.1 and No.2 pins of the  
CNS2 on the control board. 
Check the wiring between the control board and power  
supply board for the transmission line (CN102 and CNIT),  
and check for proper connection of connectors. 
Check the wiring between the control board and power  
supply board for the transmission line (CN102 and CNIT),  
and check for proper connection of connectors. 
Is there a wiring  
error or a connector  
disconnection? 
Check the voltage between No.5 and No.2 pins  
of the CNIT on the control board. 
Is the voltage  
measurement between 
 4.5 and 5.2 VDC? 
Is there a connector  
disconnection? 
Fix the connector disconnection. 
Replace the M-NET board 
Replace the M-NET board 
Replace the inrush current  
limiting resistor. 
Replace the INV board.  
Replace the INV board.  
Check the wiring between the noise filter and the  
INV board as well as screw tightness, and fix any  
problems found. 
Replace the noise filter. 
Check and fix any power supply wiring and main power  
supply problems found. 
Check the inrush current resistance (R1). 
Fix the wiring and connector  
disconnection. 
Check for shorted transmission  
line for centralized control. 
Replace the control board. 
Check the voltage between No.1 and No.2 pins of the  
CN102 on the power supply board for the transmission line. 
Check the voltage between No.1 and No.3 pins of 
the CNDC on the INV board.
Check the voltage between SC-P1 and TB-N on the INV board. 
Check the voltages among SC-R, SC-S, and 
SC-T on the INV board.
Check the voltages among TB21, TB22, and  
TB23 on the noise filter. 
Check the voltage at the power supply terminal block TB1.  
DC24 ~ 30V 
DC24 ~ 30V 
DC24 ~ 30V 
DC265 ~ 357V 
DC265 ~ 357V 
AC188 ~ 253V 
AC188 ~ 253V 
AC188 ~ 253V 
DC24 ~ 30V 
Turn on the  
power again. 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
YES 
NO 
NO 
NO 
NO 
NO 
NO 
NO 
NO 
NO 
NO 
NO 
NO 
NO
NO 
NO 
NO 
22         10% 
Check the voltage at the indoor/outdoor  
transmission terminal block (TB3) of outdoor unit. 
DC 24 ~ 30 V 
DC 24 ~ 30 V 
Check the voltage at TB3 after removing transmission line from TB3. 
Check whether the male connector is connected to 
 the female power supply connector (CN40). 
Connected 
Check voltage of terminal block for centralized control (TB7). 
Check voltage of TB7 by removing transmission line from TB7. 
Check if the indoor/outdoor transmission line is not 
short-circuited, and repair the problem. 
Check whether the transmission line is disconnected,  
check for contact failure, and repair the problem. 
                                    [TJMU-A]