Mitsubishi P336 User Manual

Page of 334
II  Restrictions ] 
29
- 29 -
HWE09120
GB
(4) Wiring method
1)   Indoor/outdoor transmission line
Daisy-chain terminals M1 and M2 on the terminal block 
for indoor-outdoor transmission line (TB3) on the outdoor 
units (OC, OS1, OS2) (Note), and terminals M1 and M2 
on the terminal block for indoor-outdoor transmission line 
(TB5) on each indoor unit (IC). (Non-polarized two-wire)
ŒOnly use shielded cables.
The outdoor units in the same refrigerant circuit are au-
tomatically designated as OC, OS1, and OS2 in the or-
der of capacity from large to small (if two or more units 
have the same capacity, in the order of address from 
small to large).
Shielded cable connection
Daisy-chain the ground terminal ( 
 ) on the outdoor 
units (OC, OS1, OS2), and the S terminal on the terminal 
block (TB5) on the indoor unit (IC) with the shield wire of 
the shielded cable.
2)   Transmission line for centralized control
No connection is required.
3)   MA remote controller wiring
Connect terminals 1 and 2 on the terminal block for MA 
remote controller line (TB15) on the indoor unit (IC) to the 
terminal block on the MA remote controller (MA). (Non-
polarized two-wire)
When 2 remote controllers are connected to the sys-
tem
When 2 remote controllers are connected to the system, 
connect terminals 1 and 2 of the terminal block (TB15) on 
the indoor unit (IC) to the terminal block on the two MA 
remote controllers.
ŒSet one of the MA remote controllers to sub. (Refer to 
MA remote controller function selection or the installation 
manual for the MA remote controller for the setting meth-
od.)
Group operation of indoor units
To perform a group operation of indoor units (IC), daisy-
chain terminals 1 and 2 on the terminal block (TB15) on 
all indoor units (IC) in the same group, and then connect 
terminals 1 and 2 on the terminal block (TB15) on the in-
door unit on one end to the terminal block on the MA re-
mote controller. (Non-polarized two-wire)
ŒWhen performing a group operation of indoor units that 
have different functions, "Automatic indoor/outdoor ad-
dress setup" is not available.
4)   LOSSNAY connection
Connect terminals M1 and M2 on the terminal block 
(TB5) on the indoor unit (IC) to the appropriate terminals 
on the terminal block (TB5) on LOSSNAY (LC). (Non-po-
larized two-wire)
ŒInterlock operation setting with all the indoor units in the 
same system will automatically be made. (It is required 
that the Lossnay unit be turned on before the outdoor 
unit.)
ŒRefer to "[5] 2. Manual address setup for both indoor and 
outdoor units" in the following cases: performing an inter-
lock operation of part of the indoor units in the system 
with a LOSSNAY unit, using LOSSNAY alone without in-
terlocking it with any units, performing an interlock oper-
ation of more than 16 indoor units with a LOSSNAY unit, 
or connecting two or more LOSSNAY units to indoor 
units in the same system.
5)   Switch setting
No address settings required.
(5) Address setting method
The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2.
The outdoor units are designated as OC, OS1, and OS2 in the order of capacity from large to small (if two or more units have 
the same capacity, in the order of address from small to large).
Proce-
dures
Unit or controller
Address setting 
range
Setting 
method
Notes
Factory 
setting
1
Indoor unit
Main unit
IC
No settings re-
quired.
-
To perform a group opera-
tion of indoor units that 
have different functions, 
refer to [5] 2.(page 30)
00
Sub unit
IC
2
LOSSNAY
LC
No settings re-
quired.
-
00
3
MA 
remote con-
troller
Main 
remote con-
troller
MA
No settings re-
quired.
-
Main
Sub 
remote con-
troller
MA
Sub 
remote controller
Settings to 
be made ac-
cording to 
the remote 
controller 
function se-
lection
4
Outdoor unit (Note)
OC
OS1
OS2
No settings re-
quired.
-
00