Mitsubishi P336 User Manual

Page of 334
- 34 -
II  Restrictions ]
GB
HWE09120
4.  A system in which a system controller is connected to the transmission line for centralized control and which is pow-
ered from an outdoor unit
(1) Sample control wiring
(2) Cautions
1)   ME remote controller and MA remote controller cannot 
both be connected to the same group of indoor units.
2)   No more than 2 MA remote controllers can be connected 
to a group of indoor units.
3)   Do not connect the terminal blocks (TB5) on the indoor 
units that are connected to different outdoor units with 
each other.
4)   Replacement of male power jumper connector (CN41) 
must be performed only on one of the outdoor units.
5)   Short-circuit the shield terminal (S terminal) and the 
earth terminal ( 
 ) on the terminal block for transmission 
line for centralized control (TB7) on the outdoor unit 
whose power jumper connector is mated with CN40. 
6)   A transmission booster is required in a system to which 
more than 32 indoor units (26 units if one or more indoor 
units of the 72 model or above is connected) are con-
nected.
7)   When a power supply unit is connected to the transmis-
sion line for centralized control, leave the power jumper 
connector on CN41 as it is (factory setting). 
(3)  Maximum allowable length
1)   Indoor/outdoor transmission line
Same as [5] 3.
2)   Transmission line for centralized control
L31+L32(L21) 200m 
[656ft]
3)   MA remote controller wiring
Same as [5] 1.
4)   Maximum line distance via outdoor unit 
(1.25mm
2
 [AWG16] or larger)
L32+L31+L12(L11) 500m 
[1640ft]
L32+L22(L21) 500m 
[1640ft]
L12(L11)+L31+L22(L21) 500m[1640ft]
IC 
TB5 
TB15 
1 2 
01 
IC 
TB5 
TB15 
1 2 
02 
A B 
MA 
A B 
MA 
LC 
TB5 
07 
IC 
TB5 
1 2 
TB15 
IC 
TB5 
TB15 
1 2 
05 
04 
LC 
TB5 
08 
IC 
TB5 
TB15 
1 2 
03 
A B 
MA 
IC 
TB5 
TB15 
1 2 
06 
A B 
MA 
A B 
MA 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
L12 
L11 
L22 
L21 
m3 
L31 
A B S 
L32 
Note1 
System controller 
OC 
TB3 
TB7 
51 
To be connected
To be left 
unconnected
To be left 
unconnected
m2 
m1 
OS1 
TB3 
TB7 
52 
OS2 
TB3 
TB7 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
53 
OC 
TB3 
TB7 
54 
OS1 
TB3 
TB7 
55 
OS2 
TB3 
TB7 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
M1 M2 
56 
Leave the male 
connector on 
CN41 as it is. 
SW2-1 OFF     ON
Leave the male 
connector on 
CN41 as it is. 
SW2-1 OFF     ON
Leave the male 
connector on 
CN41 as it is. 
SW2-1 OFF     ON
Leave the male 
connector on 
CN41 as it is. 
SW2-1 OFF     ON
Leave the male 
connector on 
CN41 as it is. 
SW2-1 OFF     ON
SW2-1 OFF    ON
Group Group 
Group 
Group 
Group 
Interlock operation with 
the ventilation unit 
Note1 When only the LM adapter is connected, 
           leave SW2-1 to OFF (as it is). 
Note2 LM adapters require the power supply 
          capacity of single-phase AC 208/230V. 
To be left 
unconnected
To be left 
unconnected
To be left 
unconnected
Move the male connector
from CN41 to CN40.