Mitsubishi P336 User Manual

Page of 334
III  Outdoor Unit Components ]
- 58 -
HWE09120
GB
3. INV 
board
(1) PUHY-P72TJMU-A
Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter-
minals to remove them.
IGBT 
(Rear) 
SC-P1
Rectifier diode output (P)
CN6
Open: No-load operation setting
Short-circuited: Normal setting
CN5V 
    GND 
    Output 5VDC 
LED1 
Lit: Inverter in normal operation 
Blink: Inverter error 
CN4
    GND(Fan Board)
    Serial communication signal output
CNDC 
Bus voltage output 
    P 
    N 
CN2 
   Serial communication signal output 
   GND 
   Input 17VDC 
SC-V 
Inverter output(V) 
SC-W 
Inverter output(W) 
CT22 
Current sensor(W) 
SC-U 
Inverter output(U) 
CT12 
Current sensor(U) 
SC-R 
Input(L1) 
SC-S 
Input(L2) 
SC-T 
Input(L3) 
CT3 
Current sensor(L3) 
TB-N(Note) 
Bus voltage output(N) 
TB-P(Note) 
Bus voltage output(P) 
SC-P2 
Bus voltage Input(P) 
RSH1,2 
Overcurrent detection 
resistor 
C30,31,32 
Smoothing capacitor